3
LED INDICATORS
Ch 1 through Ch 4 Status:
Associated with Inputs 1-4,
LEDs track load status. They
also show bindings in PnL.
24V Overload:
Indicates
24VDC current overload.
1 In 1
2 In 2
3 In 3
4 In 4
5 +24
6 +24
8 +24
9 GND
10 P
Cell
7
+24
3
4
LED 1
LED 2
Blue LEDs
Config.
Connect to
DLM local network
NOT Ethernet
LED 1
LED 2
Input 3
Input 4
LED 3
LED 4
24V Overload
Input 2
Input 1
2
1
LED 3
LED 4
24V Overload
POWER UP FUNCTIONALITY
LMIN-104 does not automatically bind to any loads
on initial power up. If only simple On/Off load control
is desired, loads can be assigned using standard
Push n Learn (PnL) steps.
3rd Party BAS
LMIN-104 Terminals
(1) Input 1
(2) Input 2
(3) Input 3
(4) Input 4
or
or
or
(5, 6, 7, or 8) +24VDC
(9) Common
System
Output
Power
Ground
Dry
Contact
Wattstopper Occupancy Sensor
LMIN-104 Terminals
(1) Input 1
(2) Input 2
(3) Input 3
(4) Input 4
or
or
or
Sensor
Output
(24VDC)
Power
Ground/
Common
(9) Common
Photocell Sensor
LMIN-104 Terminals
(5, 6, 7, or 8) +24VDC
(9) Common
(10) Photocell Input
(0~10V)
Power
Ground
Sensor
Output
2 Wire Momentary Switch
LMIN-104 Terminals
(1) Input 1
(2) Input 2
(3) Input 3
(4) Input 4
or
or
or
(5, 6, 7, or 8) +24VDC
NOTE:
By default, this is a toggling input
Press once
= signal sent, the Blue LED
corresponding to the input will be lit on the
LMIN-104
Press again
= the relinquish command is
sent, the Blue LED corresponding to the
input will be OFF on the LMIN-104
Maintained Switch
LMIN-104 Terminals
(1) Input 1
(2) Input 2
(3) Input 3
(4) Input 4
or
or
or
(5, 6, 7, or 8) +24VDC
TERMINAL CONNECTIONS
3 Wire Momentary Switch
LMIN-104 Terminals
(1) Input 1 for Switch 1
(3) Input 3 for Switch 2
or
or
(2) Input 2 for Switch 1
(4) Input 4 for Switch 2
(5, 6, 7, or 8) +24VDC
PUSH N LEARN
Load Binding to Inputs:
1.
Enter Push n’ Learn (PnL)
Press and hold the Configuration button on the LMIN-104 (or any other DLM device in the network) for 3 seconds. The Red LED
begins to blink rapidly. Release the configuration button. The Red LED on ALL other communicating devices begins to blink rapidly.
After 1 second, load #1 turns
ON
. All devices that are bound to this load have their blue LED solid
ON
.
2.
Load selection
Press and release the Configuration button to step through the loads. On the LMIN-104, press the buttons corresponding to Inputs
1-4 to bind the desired input to the load. When bound to the load, the LED for that input will light.
3.
Exit Push n’ Learn.
Press and hold the Configuration button for 3 seconds.
See Wiring For Sensor Input
on next page
See Photocell Mode
on page 7 for details