LEGRAND Wattstopper HB300-B Installation Instructions Manual Download Page 2

2

HBNB3 back box

 mounting requires a standard 1/2” knockout for 

the chase nipple. The box comes ready for side mounting. It can be 

modified for rear mounting as follows: 

1.  Pop out the cap in the rear knockout.
2.  Un-snap the chase nipple from the side mount and snap into 

the rear mounting hole. 

3.  Use the cap to close the side mount hole. 
4.  The chase nipple provided can be pushed into a standard 1/2” 

knockout in a metal fixture (max of 1 mm (0.04”) thick metal) 

without the need for the included internal nut. The nut can be 

used for added security if it is felt to be necessary.

5.  The Power Module mounts to the back box with a bayonet type 

fitting requiring a slight twist of the units to lock them into place.

HBNB3

Box

Long Nipple

Long Nipple

HB3xx

Sensor

Module

 *

HBLx

Lens

Alignment Guides

or

 *

Fig. 3: Mounting to Fixture with HBNB3

The HB300-B can be attached either directly to the fixture 

surface via the two screw holes provided in the Power Module 

or using the HBNB3 back box and chase nipple. The Extender 

Module (HBEM3) allows attaching the sensor to the side of 

the fixture in a number of configurations using provided chase 

nipples.

Surface mounting 

requires holes in the fixture to pass wires 

and attach two No. 6 pan head sheet metal screws through the 

surface mounting screw holes on the component side of the 

Power Module as shown.

MOUNTING OPTIONS

HB3xx

Sensor

Module

Hole 

Diameter

Fixture

Bottom

Pilot

Screw Hole 

Diameter

HBLx

Lens

Mounting

Screws

Fig. 2: Surface Mount to Fixture

WIRING

Control Output 24VDC

+24VDC

White (Neutral)

Red (Load)

Red (Line)

White

Black

Line

N

Red

Bl

k

Blue

Switch

Common

Lighting

Load

Power Pack

HB300

Red

Blac

k

Blue

Fig. 1: HB300-B Wiring

Summary of Contents for Wattstopper HB300-B

Page 1: ...me delay and PIR sensitivity The HB300 B sensors operate at 24VDC and requires a Wattstopper power pack The HB300 B basic model provides a single output to the power pack which is controlled only by o...

Page 2: ...ipple HB3xx Sensor Module HBLx Lens Alignment Guides or Fig 3 Mounting to Fixture with HBNB3 The HB300 B can be attached either directly to the fixture surface via the two screw holes provided in the...

Page 3: ...N ON ON ON 15 seconds OFF ON ON ON ON 5 minutes OFF OFF ON ON ON 10 minutes OFF OFF OFF ON ON 15 minutes OFF OFF OFF OFF ON 20 minutes OFF OFF OFF OFF OFF 30 minutes Switch 1 2 PIR SENSITIVITY OFF OFF...

Page 4: ...ture Lights will not turn OFF 1 If there is no motion from people or equipment in the sensor s view but the red LED blinks look for any nearby source of IR energy in motion such as turbulent air from...

Page 5: ...s nus visibles Assurez vous que tous les raccordements sont bien fix s 5 Fixez la lentille sur le HB300 B comme montr dans la Fig 3 6 R tablissez le courant du disjoncteur principal C BLAGE Sortie de...

Page 6: ...on de travers e Le module d extension HBEM3 permet de fixer le d tecteur sur le c t du luminaire selon diff rentes configurations l aide des manchons de travers e fournis Le montage sur la surface n c...

Page 7: ...ecteur qui peut durer jusqu une minute apr s la mise sous tension du module d alimentation ou apr s une coupure de courant de 5 minutes ou plus la charge peut tre soit activ e soit coup e en fonction...

Page 8: ...Une lentille HBL L indique le num ro de la lentille voir GUIDE DES PORT ES HB300C B Con us pour les applications temp rature ambiante froide 40 55 C 40 131 F HBNB3 Coffret arri re avec 2 manchons de...

Page 9: ...able pelado Aseg rese de que todas las conexiones est n aseguradas 5 Coloque la lente en el HB300 B tal como se muestra en la Fig 3 6 Restablezca la alimentaci n desde el disyuntor CABLEADO Salida de...

Page 10: ...eral del accesorio de iluminaci n con varias configuraciones utilizando los empalmes roscados provistos Para el montaje en la superficie debe haber orificios en el accesorio de iluminaci n para pasar...

Page 11: ...durar hasta un minuto despu s de aplicar energ a al m dulo de alimentaci n o despu s de un corte de energ a de 5 minutos o m s la carga puede estar ENCENDIDA o APAGADA dependiendo del estado de el rel...

Page 12: ...inistro de aire lejos del sensor o mueva el sensor 2 Verifique el tiempo de retardo El tiempo de retardo se puede configurar desde 15 segundos a 30 minutos Aseg rese de que el tiempo de retardo est co...

Reviews: