background image

2

CAUTION

WATTSTOPPER RECOMMENDS ADDING A 

20KA SURGE SUPPRESSOR TO PROTECT 

THE FIXTURE, DRIVER AND FSP SENSOR.

There are three configurations of the sensor: 

•  The FSP-321B mounts inside the fixture. 

•  The FSP-321B-S mounts to a fixture or an enclosure with a 1/2” 

knockout. 

•  The FSP-321B-D mounts to a pole or fixture.

Mounting Inside the Fixture

1.  Determine an appropriate mounting location inside the light fixture 

minimizing the electric light contribution to the sensor’s photocell. 

Allow a minimum distance of 0.2” (5.1mm) from the wiring end of 

the sensor to the wall of the fixture.

2.  Drill a hole 1.30” (33.0mm) in diameter through the sheet metal in 

the bottom of the fixture.

3.  Add the rubber gasket to the threaded collar, and install the sensor 

face down, parallel to the mounting surface. Ensure the rubber 

gasket touches the inside surface of the fixture. Install the tightening 

nut securely against the fixture to a torque of 25-30 in-lbs to ensure IP rating is maintained. 

NOTE: 

An optional collar can be installed in place of the tightening nut on the FSP-321B. This collar is included with the  

FSP-321B-S and FSP321B-D, as shown below.

Mounting to a Fixture/Enclosure – Straight Nipple

1.  Determine an appropriate mounting location minimizing the electric light contribution 

to the sensor’s photocell.

2.  If there is no knockout, drill a hole 0.875” (22mm) in diameter through the sheet 

metal in the fixture or enclosure.

3.  Add the rubber gasket to the nipple, and install the sensor face down. Ensure the 

rubber gasket touches the surface of the fixture. Install the nipple nut securely 

against the fixture to a torque of 25-30 in-lbs to ensure IP rating is maintained. 

Mounting to a Pole or Fixture – Drop Nipple 

1.  Determine an appropriate mounting location on the pole.

2.  Drill a hole 0.875” (22mm) in diameter through the pole.

3.  Add the rubber gasket to the nipple, and install the sensor face down. Ensure the 

rubber gasket touches the surface of the fixture. If needed, add the nut between the 

sensor body and the rubber gasket to ensure a secure fit. Install the nipple nut securely 

against the fixture to a torque of 25-30 in-lbs to ensure IP rating is maintained. 

Completing the Installation

1.  Align the locking features between the sensor and lens module and push the lens 

module forward until the o-ring seals firmly. Turn the lens module clockwise to 

ensure it locks in place.

2.  Connect wires as shown in wiring diagram.

3.  Restore power from the circuit breaker.

NOTE: 

The IP66 rating for this unit is based on proper installation as indicated above. 

However, as Fixture housings may vary in thickness, material, and hole dimensions 

to accommodate this unit, all precautions to maintain IP66 should be considered 

with the combination and installation of the unit to the Fixture Housing. This includes 

installation to an IP66 rated Fixture Housing and use of suitable outdoor rated 

silicone seals or accessories.

Tightening Nut

(or Optional Collar)

Fixture 

Wall

Lens Assembly

Outside 

Fixture Wall

Inside Fixture

Wall

Mounting Within Fixture

Tightening Nut

(or Optional Collar)

Rubber

Gasket

Rubber

Gasket

1

2

INSTALLATION

WARNING

TURN THE POWER OFF AT THE CIRCUIT 

BREAKER BEFORE INSTALLING THE SENSOR.

Straight Nipple Mount

Nipple

Rubber 

Gaskets

Nipple

Nut

Drop Nipple Mount

Nipple

Nut

Nipple

Rubber 

Gaskets

Drop Nipple Mount

Nipple

Rubber 

Gaskets

Nipple

Nut

Nut

NOTE: 

The Outside Fixture Wall thickness should be no 

greater than 0.125” (3.18mm) for optimal sensor 

mounting and security.

LENS OPTIONS

Several lenses are available for use with the FSP-321B. Lenses give coverage at mounting heights between 8’ - 40’ for applications 

such as, offices, warehouses and outdoor use. Density and range of the coverage is determined by the type of lens and mounting 

height. A lens with shroud option is also available. The shroud blocks light coming from the fixture, to prevent interference with the 

photocell function of the sensor. Lens modules are IP-66 rated when combined with an FSP-321B sensor mounted to an outdoor rated 

fixture. See the FSP-Lx Coverage Guide for more information. 

Summary of Contents for Wattstopper FSP-321B

Page 1: ...fc Continuous Dimming Disabled 0 250 fc Factory Defaults High Mode 10 V Low Mode 1 V Time Delay 5 min Cut Off 1 hr Sensitivity High Hold Off Setpoint Disabled Ramp Up Disabled Fade Down Disabled Photo...

Page 2: ...face of the fixture If needed add the nut between the sensor body and the rubber gasket to ensure a secure fit Install the nipple nut securely against the fixture to a torque of 25 30 in lbs to ensure...

Page 3: ...s Search Wattstopper Sensor Config on your device to download NOTE Bluetooth communication ranges can vary depending on the device as well as mobile carrier Wattstopper recommends devices with Bluetoo...

Page 4: ...button allows you to stop the update However be careful selecting this because it could leave the sensor in a non functional state at which point you will have to start the update process and allow it...

Page 5: ...t discover the sensor on the app If you do not connect with the sensor for 7 days after being powered on the radio stops broadcasting Power cycle the sensor in order to enable the radio ORDERING INFO...

Page 6: ...At least 20 cm of separation distance between this device and the user s body must be maintained at all times Any changes or modifications not expressly approved by The Watt Stopper Inc could void the...

Page 7: ...raccord situ l arri re Le FSP 321B D a un raccord de fixation suspendu pour l installation sur un poteau ou sur un luminaire Le d tecteur utilise la technologie de d tection par infrarouge passif IRP...

Page 8: ...caoutchouc au raccord et installez le d tecteur face vers le bas Assurez vous que le joint en caoutchouc touche la surface du luminaire Si n cessaire ajoutez ll crou entre le corps du d tecteur et le...

Page 9: ...bile Wattstopper recommande des appareils avec Bluetooth 5 0 Les appareils Iphone 8 et Samsung Galaxy S8 et versions ult rieures sont recommand s pour des performances optimales L outil de configurati...

Page 10: ...r cente est disponible et que vous souhaitez mettre jour le d tecteur appuyez sur D marrer la mise jour Un cran de progression affichera la progression de la mise jour Une fois termin l affichage ind...

Page 11: ...l du niveau de lumi re de la cellule photo lectrique J ai oubli mon mot de passe Maintenez le bouton de r initialisation sous l objectif du capteur pendant 15 secondes Cela r initialisera l appareil a...

Page 12: ...tilisateur doivent tre maintenu en tout temps Tout changement ou modification non express ment approuv par The Watt Stopper Inc pourrait annuler le droit de l utilisateur utiliser l quipement D CLARAT...

Page 13: ...D posee una boquilla de montaje de ca da para montar en un polo o en un aplique Los sensores usan tecnolog a de detecci n de infrarrojo pasivo PIR que reacciona a los cambios de energ a infrarroja te...

Page 14: ...ma a la boquilla e instale el sensor boca abajo Aseg rese de que la junta de goma toque la superficie de la luminaria Si es necesario agregue la tuerca entre el cuerpo del sensor y la junta de goma pa...

Page 15: ...retardo corte y m s Con la aplicaci n Sensor Configuration tambi n puede establecer y almacenar perfiles de par metros FSP 321B y habilitar la atenuaci n continua La aplicaci n m vil Sensor Configura...

Page 16: ...la aplicaci n Si hay una versi n m s nueva disponible y desea actualizar el sensor toque Iniciar Actualizaci n Una pantalla de progreso mostrar el progreso de la actualizaci n Una vez finalizado la pa...

Page 17: ...el LED parpadea 3 veces el sensor ha alcanzado su punto de configuraci n del Nivel de Luz Fotocelda Se me olvid mi contrase a Mantenga pulsado el bot n de reinicio bajo la lente del sensor durante 15...

Page 18: ...osici n a radiofrecuencia RF la FCC e IC para dispositivos m viles Este dispositivo solo est autorizado para su uso en una aplicaci n m vil Al menos 20 cm de distancia de separaci n entre este disposi...

Page 19: ...ion ou la performance de ce produit ou tout autre dommage indirect li la perte de propri t de revenus ou de profits ou aux co ts d enl vement d installation ou de r installation WattStopper garantiza...

Reviews: