LEGRAND Wattstopper FSP-212 Installation Instructions Manual Download Page 4

4

Mode D – Indoor Parking Structure or High-Bay 

Features: At dusk, turns ON with occupancy; High Dim Level sets Maximum ON level; 

OFF at dawn

When the ambient lighting is below daylight control level and occupancy is detected, the load 

turns ON at the level set with the 

Dim

 pot. Once no occupancy is detected and the time delay 

expires, the load will turn OFF. Once ambient lighting rises to the daylight control level, the 

load will turn OFF.

Mode E – Service Mode

Features: Allows visual adjustment of Dimming Level

If the 

Time

 pot is set at maximum, the load turns ON at the current 

Dim

 level. If the 

Time

 pot 

is set at minimum, the load turns OFF. 
Note that after turning the Time pot to change the ON/OFF setting, the unit will not respond to 

further changes for 3 seconds.

Test Mode

Test mode sets the time delay to 5 seconds to allow for testing the occupancy sensor.
Whenever Mode C is selected using the 

Mode

 pot, the FSP-212 will enter Test mode for 5 

minutes. If the FSP-212 is currently in mode C, selecting another mode and then returning to mode C will restart Test mode. During 

Test mode, daylight control is not active and the value of the Time pot is overridden. When occupancy is detected the load will turn 

ON at 10V. Once no occupancy is detected, the load will got to the dim level after 5 seconds, and then will stay at the dim level for 2.5 

seconds, before turning OFF. After 5 minutes, the unit will revert to normal Mode C operation.

Daylight Control

High/Low Dim

Time Delay

Auto On

Auto Off

Mode A*

Yes

Low Dim
Default Level – Min. (1V)

30sec – 30 min
Default – 15 min.

Ambient light level below 

daylight control level

Ambient light level above 

daylight control level

Mode B

Yes

Low Dim

30sec – 30 min
1/2 of set value 

during Low Trim

Ambient light level below 

daylight control level and 

occupancy detected

One half time delay expired 

or ambient light level above 

daylight control level

Mode C

No

Low Dim

30sec – 30 min
1/2 of set value 

during Low Trim

Occupancy detected

One half time delay expired

Mode D

Yes

High Dim

30sec – 30 min

Ambient light level below 

daylight control level and 

occupancy detected

Time delay expired or 

ambient light level above 

daylight control level

Mode E

No

Low Dim

Not applicable

Load is ON at Dim level 

when time delay trim in 

maximum position

Load is OFF when time 

delay trim in minimum 

position

* Default Mode Setting

TROUBLESHOOTING

Lights do not turn ON at Full Value:

•  Make sure that the sensor is not obstructed.
•  If Mode is set to A or B, check light level parameter, to find out the amount of light that the sensor is detecting. Cover the sensor 

lens to simulate darkness in the room. If the lights come ON, the ambient light level is too high.

•  If the red LED blinks 1 time per second, the FSP-212 is in short circuit protection mode.
•  If the red LED blinks 2 times per second when the sensor is triggered, and in modes A, B, or D, the ambient light level is too high.
•  Make sure the FSP-212 is not set to Mode E (Service mode) and time delay trim is not at minimum position.
•  If lights still do not turn ON, call 800.879.8585 for technical support.

Lights will not go to Dimming Level:

•  Check all wire connections and verify the dimming wires are tightly secured.
•  Make sure that the sensor is not obstructed.
•  If Mode is set to D, check light level parameter, to find out the amount of light that the sensor is detecting. Cover the sensor lens to 

simulate darkness in the room. If the lights go the dim level, the ambient light level is too high.

•  The time delay can be set from a minimum of 30 seconds to a maximum of 30 minutes. Ensure that the time delay is set to the 

desired delay and that there is no movement within the sensor’s view for that time period.

•  To quickly test the unit operation, enable test mode and move out of the sensor’s view. Lights should fade to the dim level  after 5 

seconds and then turn OFF after 2.5 seconds.

0

10

Day

Day

Night

Dim

Occupancy

Time Delay

Mode D

0

10

Dim

Mode E

Applies Day or Night

Time Delay

set to maximum

Time Delay 

set to minimum

3 seconds needed between changes

Summary of Contents for Wattstopper FSP-212

Page 1: ...vides easy to use selectable modes with several adjustable parameters The FSP 212 offers four different control modes of operation plus service and test modes that can be selected using a rotary pot O...

Page 2: ...4 for details Snap In Mounting 1 Cut a rectangular hole 32 6mm 0 2mm by 89 9mm 0 2mm through the sheet metal in the bottom of the fixture The surface of the bottom of the fixture must be between 75mm...

Page 3: ...de E and Test Mode fade up and fade down time is 0 seconds Mode A Outdoor Parking Area Keeping Minimum Light Level at Night Features Always ON during the night ON at dusk Low Dim maintains minimum lev...

Page 4: ...min 1 2 of set value during Low Trim Occupancy detected One half time delay expired Mode D Yes High Dim 30sec 30 min Ambient light level below daylight control level and occupancy detected Time delay...

Page 5: ...ambient temperature conditions so ensure the installed location has good ambient temperature If lights still do not turn OFF call 800 879 8585 for technical support ORDERING INFORMATION Catalog Descr...

Page 6: ...rents en plus des modes service et test qui peuvent tre s lectionn s avec un potentiom tre rotatif Une fois d marr chaque mode poss de un ensemble de param tres r gl s par d faut De plus les r glages...

Page 7: ...nts de verrouillage entre le capteur et le module de lentille et poussez le module de lentille vers l avant jusqu ce que les joints toriques soient fermement scell s Tournez la lentille dans le sens d...

Page 8: ...anent fois 0 secondes Mode A Zones de stationnement ext rieur maintenant un niveau de lumi re minimum durant la nuit Caract ristiques Toujours en marche durant la nuit en marche au cr puscule la grada...

Page 9: ...rche en mode automatique Arr t automatique Mode A Oui Gradation faible Niveau par d faut Min 1V 30 sec 30 min D faut 15 min Niveau de lumi re ambiante sous le niveau de r gulation de la lumi re du jou...

Page 10: ...condes Si les lumi res ne s teignent toujours pas consultez Niveau de gradation ou appelez au 1 800 879 8585 pour obtenir du soutien technique Les lumi res ne s teignent pas Veillez ce que le FSP 212...

Page 11: ...uatro modos de control de funcionamiento diferentes m s modos de prueba y de servicio que se pueden seleccionar mediante el uso de un potenci metro giratorio Una vez activado cada modo tiene un conjun...

Page 12: ...ADO Balasto Regulador Controlador L NEA NEUTRO NEUTRO GRIS VIOLETA CARGA Balasto No Regulador L NEA NEUTRO NEUTRO CARGA Nota Funcionamiento de nivel de atenuaci n queda desabilitado cuando se cablea d...

Page 13: ...tinuaci n se apaga despu s del retardo apagado en la madrugada Cuando la luz ambiental se encuentra por debajo del nivel de control de luz diurna y se detecta la ocupaci n el sensor enciende las carga...

Page 14: ...or establecido durante el ajuste bajo Ocupaci n detectada Medio retardo de tiempo caducado Modo D S Regulaci n baja 30 s 30 min Nivel de luz ambiental por debajo del nivel de control de luz diurna y s...

Page 15: ...dos y luego se apagar n despu s de 2 5 segundos Si las luces todav a no bajan al nivel de regulaci n llame al 800 879 8585 para obtener soporte t cnico Las luces no se apagan Aseg rese de que la unida...

Reviews: