Wattstopper

 

®

Vacancy Sensor Switch (v2)
Interrupteur de détecteur d’inoccupation (v2)
Interruptor del sensor de vacantes (v2)

Installation Instructions • Instructions d’Installation • Instrucciones de Instalación

No: 24218 – 07/20  rev. 2

Catalog Number • Numéro de Catalogue • Número de Catálogo: CS-50

Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China

SPECIFICATIONS

Voltage .................................................................... 120VAC, 60Hz
Load (Single Pole Circuit)
 

Incandescent, Fluorescent, E-Ballast, or LED ...... 0-600 Watt 

Fan motor ..............................................................................1/6 hp
Time Delay .............................................30 seconds to 30 minutes
Environment ........................................................... Indoor use only
Operating Temperature ...........................32° to 131°F (0° to 55°C)
Humidity .................................................95% RH, non-condensing
Storage Temperature .............................. 5F to 158F (-15C to 70C)
Tools Needed
Insulated Screwdriver
Wire Strippers

Cover plate not included

DESCRIPTION AND OPERATION

The CS-50 Vacancy Sensor is designed to replace a standard light or fan switch. The sensor uses passive infrared technology to sense 

human motion in a space and turn the light OFF when the room is vacant. It is ideal for applications where there is a direct line of sight 

from the sensor to the room. 
Like a standard switch, pressing the ON/OFF button will turn the light or fan (controlled load) ON and OFF. Unlike a standard switch, 

the CS-50 automatically turns OFF the controlled load after the coverage area has been vacant for a period of time known as the Time 

Delay. If motion is detected within 30 seconds after it automatically turns OFF, the CS-50 automatically turns the load back ON.

Indicator Light

The Status LED located on the ON/OFF button blinks upon initial detection.  It will blink again when it detects a change of infrared 

energy in the space. The LED can be disabled. See 

Status LED

.

INITIAL POWER UP DELAY

There is an initial warm-up and calibration period the first time power is applied to the unit after a power failure lasting more than 5 

minutes, and after the load is replaced.

COVERAGE AREA 

The CS-50 has a maximum coverage range of 180 degrees and a coverage area of 600 square 

feet (56 square meters). The sensor must have a clear and unobstructed view of the coverage 

area. Objects blocking the sensor’s lens may prevent detection thereby causing the light to turn off 

even though someone is in the area.

NOTE: Windows, glass doors, and other transparent barriers will obstruct the sensor’s 

view and prevent detection.

Fig 1: Sensor Coverage Area

P

P

Summary of Contents for Wattstopper CS-50

Page 1: ...to the room Like a standard switch pressing the ON OFF button will turn the light or fan controlled load ON and OFF Unlike a standard switch the CS 50 automatically turns OFF the controlled load afte...

Page 2: ...ated copper GROUND wire from the circuit to the green ground wire on the CS 50 Make sure there is a solid ground connection Connect the power wire from the circuit HOT to the black wire on the CS 50 C...

Page 3: ...c 30min 5m in 10min 20min 11543r1 Fig 5 Remove Front Cover Adjusting the Time Delay The factory setting for the time delay dial is fully clockwise providing the maximum delay of 30 minutes To reduce t...

Page 4: ...for that time period To quickly test the unit for proper operation turn the time delay to minimum and move out of the sensor s view Lights should turn off after 30 seconds Press the ON OFF button If...

Page 5: ...obstacles transparents bloqueront le d tecteur capteur et emp cheront le dispositif de fonctionner Fig 1 Zone de port e du d tecteur P P INSTRUCTIONS EN FRAN AIS DESCRIPTION ET FONCTIONNEMENT Le d te...

Page 6: ...e terre vert du CS 50 Assurez vous de la fiabilit de la mise la terre Raccordez le fil d alimentation du circuit SOUS TENSION au fil noir du CS 50 Raccordez le fil d alimentation de la lampe ou du ven...

Page 7: ...murale 2 Saisissez fermement les bords de la protection avant directement en dessous de la lentille au niveau de l inscription open ouvrir voir la figure 5 Poussez un c t en premier jusqu ce qu il se...

Page 8: ...du dispositif r glez le d lai de temporisation sur le minimum et sortez de la zone couverte par le d tecteur de mouvement La lumi re doit normalement s teindre au bout de 30 secondes Appuyez sur l int...

Page 9: ...o incluyendo el apagar la luz aunque haya persona dentro del espacio NOTA Ventanas puertas de vidrio y otras barreras transparentes obstruir n la cobertura del sensor y evitar n que haya detecci n P P...

Page 10: ...l sensor CS 50 utilizando los conectores wire nuts provistos de acuerdo al diagrama Fig 4 Conecte el cable verde o alambre de cobre sin aislante que conecta a TIERRA al Cable verde del CS 50 Aseg rese...

Page 11: ...1543r1 OPEN OPEN 30sec 30min Ajuste del Retardo de Apagado El ajuste de la perilla de retraso de tiempo es hacia a la derecha proporcionando el retardo m ximo de 30 minutos Para reducir la cantidad de...

Page 12: ...tor 2 Agarre con firmeza los lados de la cubierta delantera abajo del lente donde dice Open Ver Fig 5 Apriete un lado primero hasta que salga luego haga lo mismo con el otro lado Retire la cubierta de...

Reviews: