FCC ID:  PII-RDS2000
This device complies with Part 15 of the FCC Rules. Operation is subject 
to the following two conditions:  (1) This device may not cause harmful 
interference, and (2) this device must accept any interference received, 
including interference that may cause undesired operation. 
 
NOTE: This equipment has been tested and found to comply with the 
limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. 
These limits are designed to provide reasonable protection against 
harmful interference in a residential installation. This equipment 
generates, uses and can radiate radio frequency energy and, if not 
installed and used in accordance with the instructions, may cause 
harmful interference to radio communications. However, there is no 
guarantee that interference will not occur in a particular installation. If 
this equipment does cause harmful interference to radio or television 
reception, which can be determined by turning the equipment off and 
on, the user is encouraged to try to correct the interference by one or 
more of the following measures: 
-- Reorient or relocate the receiving antenna. 
-- Increase the separation between the equipment and receiver. 
-- Connect the equipment into an outlet on a circuit different from that 
to which the receiver is connected. 
-

Consult the dealer or an experienced radio/TV technician for help. 

 
Changes or modifications to this product not expressly

 approved by 

Vantage Controls could void the user’s authority to operate 
this product.

 

Reset  
The station stores the configuration data locally so that it will 
continue to operate if communication with the system is lost. This 
information includes: LED properties and sounder properties. To 
reset this information to the factory default, press and hold 
switches 1, 2 and 3 while power is applied to the station. The status 
LED flashes briefly, indicating that the reset took place. After a 
reset, the loads will be off and the LEDs will change to Blue for ON 
and White for OFF. If the station was used as a Shade Controller 
the 

Full Open

 and 

Full Closed

 positions must be re-learned by fully 

opening and then fully closing the blind without stopping. 
 
Removing Metal Tabs 
Removal of metal tabs allows ganging with other ScenePoint 
Stations or third party devices.  
 
Diagnostic Information 
The Status LED can be seen behind the sensor light bar. The sensor 
bar is just between the bottom two buttons. The Status LED is off 
or blinks 2, 3, 4 or 5 times followed by a pause to indicate status 
information. 
 
Off: The station is programmed and configured, or the station is 
not powered, a line voltage connection has not been made or the 
line feed breaker is off.  
Two blinks: Station has logged on to Controller but is not 
initialized. If two blinks persist more than five minutes, the station 
should be reset. See Reset above. 
Three blinks: Station is not added to the network. Verify that its 
serial number has been programmed into the Controller and that 
the station is within 100 Feet of the RFE1000. 
Four blinks: Relay station problem.  Please contact the factory. 
Five blinks: Configuration mode.  
 

Cleaning Buttons and Faceplates 

 

Turn the breaker to the station OFF 

 

Dampen a soft cloth in water and wring-out to barely 
damp – almost dry 

 

Use a light buffing motion to wipe clean 

 

Do not take the station apart 

 

Never spray station with any cleaners 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
ScenePoint Wiring Examples 
 
 
Motorized Blind 

 Always disconnect power before wiring 

the station and shade motor. In this 
application the Interlock Switch is set to 

active

 or Interlocked. Connect load 1 to the 

open relay of the blind motor and load 2 to 
the close relay, or vice-versa. Typically, 
neutrals are all tied together at the station 
box. Custom program desired operation in 
Design Center. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Fan and Light 

 

 Always disconnect power before wiring the 

station and station loads. In this application the 
Interlock Switch is set to inactive or the non-
interlocked switch position. Connect relay load 1 to 
the light and relay load 2 to the fan, or vice-versa. 
Typically, neutrals are all tied together at the station 
box. Custom program desired operation in Design 
Center. 
NOTE: The light may not be dimmed in this 
application. 

 