SmartLock Kit Quick Setup Guide - DX2-DH2C2
6
SmartLock_DX2DH2C2_QSG_1G_3.6.10
255-90-0006-00
•
After these configurations, return to the Peripherals Devices page. This page now displays state, type and Position options for each
configured component.
Optional Setting: Unlock Front and Rear Doors Simultaneously
By default, the PDU configuration is set to unlock only one lock at a time to preserve power. You must change the Active Powered Dry Contact
Limit to 2 if you require unlocking the front and rear door simultaneously at the rack.
•
Click PDU in the Main menu. Click Edit and change the setting as shown.
Note: With some door handles, while you open and close one door handle, the second door handle is powered off briefly to conserve power.
Once the first door handle is closed and locked, power resumes to the second handle and it is ready to use.
Power IQ Integration
If you are integrating SmartLock with Power IQ, you will need to do additional configurations to complete integration.
Power IQ relies on traps sent by your PDU to get the card reader events. Configure your PDU to forward card reader management related events
to Power IQ. See the online help for your PDU for further instructions on SNMP Settings and Event Rule Settings.
Once the configurations described in this guide are complete, Power IQ will have the required infrastructure support to implement a solution
with card authorization for unlocking cabinet doors. The following additional configurations are required on Power IQ to accomplish this:
•
Card Access Management: Add and assign cards to users
•
Add PDUs in Power IQ