background image

 

 

 

 

SmartLock Kit Quick Setup Guide - DX2-DH2C2 

SmartLock_DX2DH2C2_QSG_1G_3.6.10 

 255-90-0006-00 

 

 

 

 

 

SmartLock with DX2-DH2C2 

Model Number: DX2-DH2C2 

Raritan’s SmartLock is an electronic door access and control system for all types of data center enclosures.   

 

Supported Components 

DX2-DH2C2 door handle controller supports the following components: 

PDU 

PX3 
PX3TS 
PXC 
SRC 
Legrand PDU 

Xerus 

3.6.10 and up 

Door Handles 

Southco H3-EM-60-100 
Southco H3-EM-62-100 
Southco H3-EM-64-100 
Southco H3-EM-65-100 
Southco H3-EM-66-100   
Southco H3-EM-67-100   
Southco H3-EM-68-100 

Emka Agent E 
Emka 1150-U5x 
Dirak eLine MLR1000 
Dirak eLine MLR2X00 

 

 

Restrictions for DX2-DH2C2 

 

Always connect DX2-DH2C2 directly to the sensor port. If you are cascading with other sensors, the DX2-DH2C2 must be in the first position, 

directly connected to the sensor port. 

 

Max. of 1 DX2-DH2C2 with up to 2 electronic door handles per Sensor port 

 

Max. cable length PDU to DX2-DH2C2: 5m 

 

Max. cable length DX2-DH2C2 to door handle: 4m 

 

No support for hot-plugging door handles. Door handle must not be plugged or unplugged from DX2-DH2C2 while contacts are powered. 

Risk of equipment damage. 

 

More Info 

Raritan Product Support:   
https://www.raritan.com/support/product/px3 

 

SMARTLOCK QUICK SETUP GUIDE 

 

Summary of Contents for Raritan SmartLock DX2-DH2C2

Page 1: ...H3 EM 67 100 Southco H3 EM 68 100 Emka Agent E Emka 1150 U5x Dirak eLine MLR1000 Dirak eLine MLR2X00 Restrictions for DX2 DH2C2 Always connect DX2 DH2C2 directly to the sensor port If you are cascadi...

Page 2: ...r handle ports Use wiring provided with your door handles Connect the 8 pin connector end to the door handle port CONTACT CLOSURE Contact closure sensor channels CC sensors and wiring not included Con...

Page 3: ...e physical connections are complete login to your PX PDU to use door handle features in the web interface Web Configuration Peripherals Click Peripherals in the Main menu to view the sensors that have...

Page 4: ...QSG_1G_3 6 10 255 90 0006 00 SmartLock Click Smart Lock in the Main menu to open the Door Handle options Smart Lock Controller section on top displays the physical connection to the DX2 DH2C2 Door Han...

Page 5: ...act is closed conducting when the door is closed and open not conducting when the door is open Default Normally open The contact not conducting when the door is closed and conducting when the door is...

Page 6: ...le is powered off briefly to conserve power Once the first door handle is closed and locked power resumes to the second handle and it is ready to use Power IQ Integration If you are integrating SmartL...

Page 7: ...T SML KIT EKA AGE 2D 2 EKA AgentE DX2 DH2C2 SML KIT SCO 60 2D 2 H3EM 60 DX2 DH2C2 SML KIT EKA AGE 1DL 1 EKA AgentE L DX2 DH2C2 SML KIT SCO 62 2D 2 H3EM 62 DX2 DH2C2 SML KIT EKA AGE 2DL 2 EKA AgentE L...