40
EN
PREMIUS
1-10 kVA
Specifications 5-10 kVA Without Isolation Transformer
Rating Capacity (kVA/kW)
5 kVA/5 kW
6 kVA/6 kW
7.5 kVA/7.5 kW
10 kVA/10 kW
INPUT
Voltage
Range
Voltage – Low
Transfer
110/140/160 VAC ± 5 V
(Based on load percentage 0 ~ 60% / 61 ~ 80% / 81 ~ 100%)
Voltage – Low
Comeback
135/165/185 VAC ± 5 V
(Based on load percentage 0 ~ 60% / 61 ~ 80% / 81 ~ 100%)
Voltage – High
Transfer
300 VAC ± 5 V
Voltage – High
Comeback
285 VAC ±5 V
Frequency
45 ~ 70 Hz
Phase/Wire
Single-in, Line + N Ground
Input Connection
75A 4W Terminal Block
100A 4W Terminal Block
Power Factor
Up to 0.99 at 100% Linear Load
Current THD (100% linear load)
<5%
OUTPUT
Voltage
220/ 230/ 240 VAC Selectable
Frequency Regulation
±1 Hz, ±3 Hz Selectable
Voltage Regulation
±1%
Rated Power Factor
1.0
Output Connection
75A 3W Terminal Block
100A 3W Terminal Block
Sine
Waveform
Distortion
100% Liner Load
<2%
100% Non-Liner
Load
<5%
Frequency Stability
<0.2% (Free Running)
Transfer Time AC-DC
0 ms
Transfer Time
(Inverter to Bypass)
4 ms
Crest Factor
3:1
Overload Capacity
(tolerance±1%)
<105% continuous
106-110% UPS works with warning at battery mode and in utility mode.
111-130% UPS shuts down after 5min at battery mode or transfer to bypass
when the utility is normal.
131-150% UPS shuts down after 1min at battery mode or transfer to bypass
when the utility is normal
>150% Immediately trip at battery mode or transfer to bypass when the utility
is normal
7 Specifications
Summary of Contents for PREMIUS
Page 1: ...PREMIUS 1 10 kVA User and Installation Manual ...
Page 13: ...13 2 3 2 Rear Panel 1 kVA 3 kVA FMI 3 kVA FM 2 kVA FMI 2 kVA FM 1 kVA FMI ...
Page 14: ...14 EN PREMIUS 1 10 kVA 5 kVA 6kVA FMI 5 kVA 6kVA FM 7 5 kVA 10kVA FM 7 5 kVA 10kVA FMI ...
Page 39: ...39 6 Optional Interface Cards 6 1 RSE F RS 485 card 6 2 DCE Dry Contact 6 3 SNMP Card ...
Page 50: ......