LEGRAND NUMERIC Onfiniti User And Installation Manual Download Page 6

1.  External battery connector
2.  RS-232 communication port
3.  Intelligent slot
4.  USB communication
5.  Emergency power off function connector (EPO connector)
6.  Cooling fan 1
7.  Input circuit breaker
8.  Input/Output terminal (Refer to Diagram 2, 4, 6, 8, 10 and 12 for details)
9.  Output terminal
10.  Grounding terminal
11.  Utility input terminal
12.  Cooling fan 2

2-3  Single UPS Installation
Installation and wiring must be performed in accordance with the local electric laws/regulations and the 

following instructions should be executed by professional personnel.

1)  Make sure the mains wire and breakers in the building are in compliance with the standard of rated capacity 

of UPS to avoid hazards of electric shock or fire.

Note: Do not use the wall receptacle as the input power source for the UPS, as its rated current is less than the 

UPS maximum input current. This could lead to receptacles being burnt and damaged.

2)  Switch off the mains switch in the building before installation.
3)  Turn off all the connected devices before connecting to the UPS.
4)  Prepare wires based on the following table:

Model

Wiring spec. (AWG/mm

2

)

Input

Output

Battery

Ground

5/6 kVA FM - Standard

6/10

10/6

10/6

6/10

5/6 kVA FM - S1 charger

4/16

10/6

10/6

6/10

5/6 kVA FM - S2 charger

4/16

10/6

10/6

6/10

5/6 kVA FM - S3 charger

4/16

10/6

10/6

6/10

5/6 kVA FMI - Standard

6/10

10/6

10/6

6/10

5/6 kVA FMI - S1 charger

4/16

10/6

10/6

6/10

Model

Wiring spec. (AWG/mm

2

)

Input

Output

Battery

Ground

5/6 kVA FMI - S2 charger

4/16

10/6

10/6

6/10

5/6 kVA FMI - S3 charger

4/16

10/6

10/6

6/10

7.5/10 kVA FM - Standard

4/16

8/10

8/10

4/16

7.5/10 kVA FM - S1 charger

4/16

8/10

8/10

4/16

7.5/10 kVA FM - S2 charger

2/25

8/10

8/10

4/16

7.5/10 kVA FM - S3 charger

2/25

8/10

8/10

4/16

7.5/10 kVA FMI - Standard 

4/16

8/10

8/10

4/16

7.5/10 kVA FMI - S1 charger

4/16

8/10

8/10

4/16

7.5/10 kVA FMI - S2 charger

2/25

8/10

8/10

4/16

7.5/10 kVA FMI - S3 charger

2/25

8/10

8/10

4/16

5)  Remove the terminal block cover on the rear panel of the UPS. Connect the wires according to the following 

terminal block diagrams: 

  (Connect the earth wire first when making wire connection. Disconnect the earth wire last when making 

wire disconnection.)

 

Terminal block wiring diagram for 6 kVA/10 kVA

Note 1:  Make sure that the wires are connected tightly with the terminals. 
Note 2:  Please install the output breaker between the output terminal, the load and the breaker   

 

should be qualified with leakage current protective function if necessary.

6)  Put the terminal block cover back to the rear panel of the UPS.

 

Warning

 

Make sure a DC breaker or other protection device between UPS and external battery pack is installed.

 

If not, please install it carefully. Switch off the battery breaker before installation.

 

Warning 

 

For standard battery pack, there is one DC breaker to disconnect the battery pack and the UPS. But 

for other external battery pack, make sure a DC breaker or other protection device between UPS and 

external battery pack is installed. If not, please install it carefully. Switch off the battery breaker before 

installation.

Note: Set the battery pack breaker in ‘OFF’ position and then install the battery pack.

 

Input Neutral 

Input Line 

Ground 

Output Line 

Output Neutral 

7

8

Summary of Contents for NUMERIC Onfiniti

Page 1: ...www numericups com NEW ENERGY TO POWER USER AND INSTALLATION MANUAL NEW ENERGY TO POWER Onfiniti 5 10 kVA www numericups com A ...

Page 2: ...4 2 3 Single UPS installation 7 2 4 Software installation 10 3 Operations 10 3 1 Button operation 10 3 2 Led indicators and LCD panel 11 3 3 Audible alarm 13 3 4 Single UPS operation 14 3 5 Abbreviation meaning in LCD display 17 3 6 LCD setting 18 3 7 Operating mode Status description 25 3 8 Fault code 26 3 9 Warning indicator 26 4 Trouble Shooting 27 5 Storage and Maintenance 28 5 1 Storage 28 5 ...

Page 3: ...2 2 Warning This is a product designed for commercial and industrial applications additional measures may be needed to prevent electrical disturbances 1 Safety and EMC Instructions Please read the following user manual and the safety instructions carefully before installing the unit or using the unit 1 1 Transportation and Storage Please transport the UPS system only in the original package to pro...

Page 4: ...I Standard 3 charger 7 5 10 kVA FMI Standard 3 charger 2 1 Unpacking and Inspection Unpack the package and check the package contents The shipping package contains One UPS One user manual One monitoring software CD One RS 232 cable optional One USB cable One battery cable optional Note Before installation please inspect the unit Be sure that nothing inside the package is damaged during transportat...

Page 5: ...t Terminal Diagram 7 7 5 10 kVA FMI Rear Panel Diagram 8 7 5 10 kVA FMI Input Output Terminal Diagram 9 7 5 10 kVA FM C Rear Panel Diagram 10 7 5 10 kVA FM C Input Output Terminal Diagram 11 7 5 10 kVA FMI C Rear Panel Diagram 12 7 5 10 kVA FMI C Input Output Terminal 5 6 ...

Page 6: ...VA FMI Standard 3 charger 4 16 10 6 10 6 6 10 7 5 10 kVA FM Standard 4 16 8 10 8 10 4 16 7 5 10 kVA FM Standard 1 charger 4 16 8 10 8 10 4 16 7 5 10 kVA FM Standard 2 charger 2 25 8 10 8 10 4 16 7 5 10 kVA FM Standard 3 charger 2 25 8 10 8 10 4 16 7 5 10 kVA FMI Standard 4 16 8 10 8 10 4 16 7 5 10 kVA FMI Standard 1 charger 4 16 8 10 8 10 4 16 7 5 10 kVA FMI Standard 2 charger 2 25 8 10 8 10 4 16 ...

Page 7: ...e sure the L N terminal is correct not reversed or short circuited 2 4 Software Installation For optimal computer system protection install UPS monitoring software to fully configure UPS shutdown 3 Operations 3 1 Button Operation Button Function ON Enter Button Turn on the UPS Press and hold the button more than 0 5 sec to turn on the UPS Enter Key Press this button to confirm the selection in set...

Page 8: ...Output Battery voltage information Indicates the output voltage frequency or battery voltage Vac output voltage Vdc battery voltage Hz frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the output is short Mode operation information Indicates the UPS connects to the mains Indicates the battery is working Indicates the Bypass ...

Page 9: ...mode 1 Make sure that the breaker of the battery pack is at ON position only for long run model 2 Press and hold the ON button for 0 5 sec to turn on the UPS and the buzzer will beep once 3 A few seconds later the UPS will be turned on and enter Battery mode 3 Connect devices to UPS After the UPS is turned on you can connect devices to the UPS 1 Turn on the UPS first and then switch on the devices...

Page 10: ... sec and then the buzzer will beep once 2 UPS will cut off power to output and there is no display shown on the display panel 9 Mute the buzzer 1 To mute the buzzer please press the Mute button for at least 0 5 sec If you press it again after the buzzer is muted the buzzer will beep again 2 Some warning alarms can t be muted unless the error is fixed Please refer to section 3 3 for the details 10 ...

Page 11: ...s AC CVCF Battery Battery Test 01 Output voltage Y 02 Output frequency Y 03 Voltage range for Bypass Y 04 Frequency range for Bypass Y 05 Reserved 06 Reserved 07 Reserved 08 Bypass mode setting Y 09 Battery maximum discharge time setting Y Y Y Y Y 10 Reserved 11 Reserved 12 Reserved 13 Battery voltage calibration Y Y Y Y Y 14 Charger voltage adjustment Y Y Y Y Y 15 Inverter voltage calibration Y Y...

Page 12: ...0 Hz or within 56 64 Hz at 60 Hz according to setting in Parameter 2 If 50 Hz selected in Parameter 2 UPS will transfer to battery mode when input frequency is not within 46 54 Hz If 60 Hz selected in Parameter 2 UPS will transfer to Battery mode when input frequency is not within 56 64 Hz If Parameter 2 is ATO the Parameter 3 will show the current frequency 03 Voltage range for bypass Interface S...

Page 13: ...etting Interface Setting Parameter 3 000 999 Set the maximum discharge time from 0 min 999 min UPS will shut down to protect battery after discharge time arrives The default value is 990 min DIS Disable battery discharge protection and backup time will depend on battery capacity 10 Reserved Interface Setting Reserved 11 Reserved Interface Setting Reserved 12 Reserved Interface Setting Reserved 13 ...

Page 14: ...rate inverter voltage Parameter 3 The voltage range is from 0 V to 6 4 V the default value is 0 V 16 Reserved Interface Setting Reserved 17 Reserved Interface Setting Reserved 18 Reserved Interface Setting Reserved 19 Reserved Interface Setting Reserved 20 Reserved Interface Setting Reserved 23 24 ...

Page 15: ...press Test key for more than 0 5 sec Then the UPS will beep once and start Battery Test The line between I P and Inverter icons will blink to remind users on the battery status This operation is used to check the battery status LCD display Fault status Description When UPS becomes faulty it will display fault messages in the LCD panel LCD display 3 8 Fault Code Fault event Fault code Icon Fault ev...

Page 16: ...ries Do not attempt to dispose of batteries by burning them This could cause battery explosion The batteries must be rightly disposed according to local regulations Do not open or destroy batteries Escaping electrolyte can cause injury to the skin and eyes It may be toxic Please replace the fuse only with the same type and amperage in order to avoid fire hazards Do not disassemble the UPS system F...

Page 17: ...20 230 240 VAC AC Voltage Regulation 1 Frequency Range Synchronized Range 46Hz 54 Hz 50Hz system 56Hz 64 Hz 60Hz system Frequency Range Batt Mode 50 Hz 0 1 Hz or 60Hz 0 1 Hz Overload AC mode 105 110 3 min 110 130 30 sec 130 1 5 sec Current Crest Ratio 3 1 max Harmonic Distortion 3 100 Linear Load 6 100 Non linear Load Transfer Time Line Battery 0 ms Inverter Bypass 0 ms BATTERY Battery Numbers 16 ...

Reviews: