Disposal
Ref standard: ISO 14001:2015
• After unpacking the UPS and Battery, the removed packaging materials like polythene paper, thermocole
/polyethylene, carton box, nylon belt, nylon thread, shall be collected and disposed through authorized
recycler.
• Batteries when found faulty/damaged, must be handed over to identified authorized recycler or to
Numeric, where it is disposed properly.
• Battery contains harmful metals and chemicals such as nickel cadmium, alkaline, mercury, nickel metal
hydride and lead acid which contaminates – if it is not disposed properly
• When batteries containing cadmium is used in fills, they will eventually dissolve and release the toxic
substance than can seep in to water supplies, posing serious health hazards, for the population/society.
Recycling batteries prevent pollution and saves resource.
6. Specifications
MODEL
5K FM C,
6K FM C
5K FMI C,
6K FMI C
7.5K FM,
10K FM
7.5K FM C,
10K FM C
7.5K FMI,
10K FMI
7.5K FMI C,
10K FMI C
CAPACITY*
5000 VA/4000 W
7500 VA/6000 W
6000 VA/4800 W
10000 VA/8000 W
INPUT
Voltage
Range
Low Line
Loss/
Comeback
160 VAC ± 5Vac at 100% Load;
140 VAC ± 5Vac at 70-80% Load;
120 VAC ± 5Vac at 60-70% Load;
110 VAC ± 5Vac at 0-60% Load;
High Line
Loss/
Comeback
300 VAC/290VAC ± 5V
Frequency Range
46Hz. ~ 54 Hz.
@
50Hz. system
56Hz. ~ 64 Hz.
@
60Hz. system
Phase
Single phase with ground
Power Factor
≥ 0.99 at 100% Load
OUTPUT
Output voltage
208/220/230/240 VAC
AC Voltage Regulation
± 1%
Frequency Range
(Synchronized Range)
46Hz. ~ 54 Hz.
@
50Hz. system
56Hz. ~ 64 Hz.
@
60Hz. system
Frequency Range
(Batt. Mode)
50 Hz. ± 0.1 Hz. or 60Hz. ± 0.1 Hz.
Overload
AC mode
105%~110%: 3 min 110%~130%: 30 sec >130%: 1.5 sec
Current Crest Ratio
3:1 max
Harmonic Distortion
≤ 3 %
@
100% Linear Load; ≤ 6 %
@
100% Non-linear Load
Transfer
Time
Line
Battery
0 ms
Inverter
Bypass
0 ms
BATTERY
Battery Numbers
16-20 (adjustable)
Current of external
Batt. pack
5000VA/4000W
6000VA/4800W
7500VA/6000W 10000VA/8000W
25A max
32A max
45A max
50A max
Charging Current
Max.: 4A ± 10% per 1 charger
Charging Voltage
(13.65VDC * N) ± 1%, “N” indicate batteries numbers
Maximum Battery AH
160
160
80
200
80
200
PHYSICAL
Dimension, DXWXH (mm) 482 x 260 x 488 482 x 260 x 871 482 x 260 x 488 482 x 260 x 535 482 x 260 x 871 482 x 260 x 918
Net Weight (kgs)
22.5
66.0
24.0
30.5
87.0
95.0
ENVIRONMENT
Operation Temperature
0-40˚C (battery life cycle will shorten when temperature is above 25˚C)
Operation Humidity
<95% and non-condensing
Operation Altitude**
<1000m
Acoustic Noise Level
Less than 55dB
@
1 meter
Less than 58dB
@
1 meter
MANAGEMENT
Smart RS-232 or USB
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix and MAC
Optional SNMP
Power management from SNMP manager and web browser
* Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208 VAC.
**If the UPS is installed or used in a place where the altitude is above 1000m, the output power will be derated by 1 percent per
100 m.
***Product specifications are subject to change without further notice.
29
30