5 Overload and self-shutdown

Your UPS is equipped with a system to measure the power delivered at the outlet; when this exceeds 

the set thresholds, the protection and relative signals are activated; shutdown is automatic with a 

delay in relation to the size of the overload.

Under the line mode the green led will be light. If the overload is 100% ± 10%; UPS will shutdown 

after 5 minutes and go to fault mode. If the overload is 110% ± 10%; UPS will shutdown immediately 

and go to fault mode.

Under the battery mode the red led will be flashed. 

If the overload is 100% ± 10%; UPS will be shutdown after 5 second and go to fault mode.

If the overload is 110% ± 10%; UPS will shutdown immediately and go to fault mode.

Self test

Automatic self text is executed each time the UPS is switched on, to provide a reliable operation.

Battery Protection

Automatic battery test and deep discharge protection.

DC start capability

The UPS can be switched on in DC mode (battery operation).

UPS power supplied outlets

This is a line interactive UPS equipped with AVR, that allows to feed the load with a stabilized 

output voltage even when mains floats.

Electrical protection

Automatic swith off upon short circuit.

CPU microprocessor control

Green function: if battery is discharging under no load, UPS will shut down automatically to save 

battery life.

EMI/RFI filtering:

Bad quality of mains supply can damage electronic appliances because of electromagnetic radio 

frequency interferences. The UPS is provided with a dedicated filter to eliminat these disturbances.

Full time surge protection outlet

Connect the appliances not needing for back up protection (printers, fax etc.) to the surge 

protected outlet located near the back of the unit.

6 Features

Summary of Contents for Niky 600

Page 1: ...800 Index 1 Introduction 14 2 Conditions of use 14 3 Installation 15 4 Signals and controls 15 5 Overload and self shutdown 16 6 Features 16 7 Changing batteries 17 8 Possible malfunctioning 18 9 Technical features 19 ...

Page 2: ... plug is disconnected there are no parts inside that the user can repair The UPS NIKY has been designed to work in closed clean rooms where there are no inflammable liquids or corrosive substances and where it is not too damp Do not place near equipments that generate strong electro magnetic fields and or near equipments that are sensible to electro magnetic fields engines floppy disks speakers ad...

Page 3: ... panel has the following meanings Fixed green LED mains present and regular batteries recharging Green LED flashing every 3 sec running on battery Green LED flashing every 0 5 sec autonomy in reserve Green red LEDs flashing test or restart after end of autonomy Fixed red LED failure or battery overload Acoustic signals Intermittent sound every 3 sec running on battery Intermittent sound every 0 5 ...

Page 4: ...on to provide a reliable operation Battery Protection Automatic battery test and deep discharge protection DC start capability The UPS can be switched on in DC mode battery operation UPS power supplied outlets This is a line interactive UPS equipped with AVR that allows to feed the load with a stabilized output voltage even when mains floats Electrical protection Automatic swith off upon short cir...

Page 5: ...ures Caution Opening repairing or replacing parts inside the UPS must always be carried out by specialized technical personnel only First of all switch off the UPS with the ON OFF button located on the front panel then unplug the power cable from the 230V outlet socket 1 Switch off the uninterruptible power supply 2 Unplug the power cable from the mains socket 3 Change the batteries with others of...

Page 6: ... shuts down or immediately signals it is close to the operating limit The UPS has operated with no mains voltage for a long time and has not been able to recharge the battery Recharge it for at least 6 hours by connecting the uninterruptible power supply to the mains The battery is flat due to not using the UPS for a long period Recharge it for at least 6 hours by connecting the uninterruptible po...

Page 7: ...densing Degree of protection as per IEC529 IP20 Noise level at 1 meter 40 dBA Electrical input specifications Rated input voltage 230 V Range of input voltage from 160 V to 290 V Rated input frequency 50 60 Hz 5Hz Maximum input current 3 75 Arms 5 Arms Number of input phases Single phase Waveform on output With battery operation step wave Type of operation line interactive Electrical specification...

Page 8: ...tery operation Operating time to 80 of the load 5 min 5 min Charging time 10 12 h at the end of operating range Technical data and number of batteries n 1 maintenance free sealed lead acid battery 12V 7 2 Ah n 1 maintanance free lead acid sealed 12V 9 Ah Standards Electromagnetic compatibility Emission Immunity Conforms to EN 62040 2 Safety Conforms to EN 62040 1 Performance and features Conforms ...

Page 9: ...elephone fax modem or network protection 4 Output sockets 5 AC Input with AC Fuse 6 USB Serial Interface 9 Technical features SITE WIRING FAULT AC INPUT AC OUTPUT IN OUT 1 1 2 4 5 3 100 09 3 100 10 3 100 02 3 100 03 6 3 100 22 3 100 23 3 4 5 6 3 4 5 6 3 ...

Reviews: