EN
19
Niky 1000/1500
9 Technical features
CONSTRUCTION SPECIFICATIONS
3 100 04
3 100 13
3 100 26
3 100 05
3 100 14
3 100 27
Weights
13 Kg.
16 Kg.
Dimensions L x H x P in mm
147 x 239 x 354
Protection
Electronic protection against overloading
and short-circuiting. Shutdown on
reaching operating limit and overheating.
Automatic shutdown due to protection
triggering
Ambient specifications
Operating temperature range
from 0 to +40 °C
Operating relative humidity range
from 0 to 95% non-condensing
Degree of protection as per IEC529
IP20
Noise level at 1 meter
< 40 dBA
Electrical input specifications
Rated input voltage
230 V
Range of input voltage
175-285VAC
Rated input frequency
50 or 60 Hz ± 1 Hz
Maximum input current
6,2 Arms
8,5 Arms
Number of input phases
Single phase
Waveform on output
With battery operation
step wave
Type of operation
line interactive
Electrical specifications on output
Rated output voltage
230 V ± 10 %
Output current on nominal load
4,7 Arms
6,5 Arms
Apparent output capacity on nominal load
600 W
900 W
Apparent output capacity on nominal load
1000 VA
1500 VA
Overload capacity
110% for 5 s.
Number of phases on output
Single phase