25
KEOR MULTIPLUG 600, 800 VA
UK
3 100 38
3 100 40
3 100 39
3 100 41
Output connections
Outlet
6 X german/italian standard with battery back
up and surge protection ( 3 100 38 / 3 100 39)
2X german/italian standard with
surge protection (3 100 40 / 3 100 41)
6 X french standard with battery back up
and surge protection (3 100 40 / 3 100 41)
2X french standard with surge protection
(3 100 40 / 3 100 41)
Short circuit protection
Line Mode
7A 250 Vac Fuse
Battery Mode
Turn off in 3 cycles
Thermal protection
Battery mode
Active @ converter > 130 ±5 degree,
recover @ converter < 75±5 degree
Efficiency
Line mode
> 95%
Battery mode
>70%
Audible noise
Line mode
<40dB
Battery mode
<45dB
Transfer
Transfer time
2~6ms Typical
Battery
Battery type
1x 12V/7Ah
1 x 12V/9Ah
Floating voltage
13.7V+/- 0.25V
Charging current
About 0.5A,max 1A
Overcharge protection
>14.5 V +/- 0.25V charger stop
Cold start Output voltage/ frequency
230V/50Hz
Summary of Contents for KEOR MULTIPLUG 600
Page 6: ...6 3 Installation IN OUT 180 mm ...
Page 9: ...9 KEOR MULTIPLUG 600 800 VA FR OFF 6 Changement des batteries ...
Page 18: ...18 3 Installation IN OUT 180 mm ...
Page 21: ...21 KEOR MULTIPLUG 600 800 VA UK OFF 6 Battery replacement ...
Page 30: ...30 3 Installazione IN OUT 180 mm ...
Page 33: ...33 KEOR MULTIPLUG 600 800 VA IT OFF 6 Sostituzione batterie ...
Page 42: ...42 3 Installation IN OUT 180 mm ...
Page 45: ...45 KEOR MULTIPLUG 600 800 VA DE OFF 6 Batterien auswechseln ...
Page 54: ...54 3 Instalación IN OUT 180 mm ...
Page 57: ...57 KEOR MULTIPLUG 600 800 VA ES OFF 6 Sustitución de las baterías ...
Page 66: ...66 3 Монтаж IN OUT 180 mm ...
Page 69: ...69 KEOR MULTIPLUG 600 800 VA RU OFF 6 Замена батареи ОТКЛ ...
Page 75: ......