KEOR LP 1, 2, 3 kVA

EN

Do not place the UPS in a dusty or corrosive environment or near any flammable objects.

This UPS is not designed for outdoor use. 

•   Keep the ventilation slits clean to dissipate the heat of the UPS.

  To prevent overheating of the UPS keep all ventilation openings free from obstruction, and do not place 

anything on top of the UPS. Keep the UPS rear panel 20 cm away from the wall or other obstructions

 

•   Use grounded power cable to connect the UPS to the mains supply.
This UPS is equipped with an EMI filter. To prevent potential leakage current hazards ensure that 

the AC mains supply is securely grounded.
•   Install the UPS close to the mains socket that supply it.The socket must be easily accessible.
•   Do not plug laser printers into the UPS because of their high start-up current.
•   Do not plug house electric equipments, such as hair dryer, air conditioner, and refrigerator into 

the UPS outlets.

-   Always switch off the UPS and disconnect the batteries when relocating the UPS. Be aware that, 

even when disconnected, charged batteries present a possible electric shock hazard.

-   The UPS should be recharged every 2-3 months if unused. When installed and being used the 

batteries will be automatically recharged 

Storage

If the UPS is unused for an extended period of time it must be stored in a moderate climate. 

The batteries should be charged for 12 hours every three months by connecting the UPS to the 

utility supply and switching on the input breaker located on the UPS rear panel. Repeat this 

procedure every two months if the storage ambient temperature is above 25°C.

40

0%~90%

200mm/

8 inch

200mm/

8 inch

200mm/

8 inch

Summary of Contents for KEOR LP

Page 1: ...LP 1 2 3 kVA EN Index 1 Introduction 26 2 Condition of use 26 3 LED Panel 28 4 Rear Panel 30 5 Installation 31 6 Functions and Signal 34 7 UPS software 39 8 Possible malfunctioning 40 9 Technical feat...

Page 2: ...UPS does not electrically isolate the internal parts To isolate your UPS unplug it from the mains power socket Do not open the UPS container since there may be parts inside with dangerously high volta...

Page 3: ...Do not plug laser printers into the UPS because of their high start up current Do not plug house electric equipments such as hair dryer air conditioner and refrigerator into the UPS outlets Always swi...

Page 4: ...Switch Press and hold until the buzzer beeps Self Test 1 2 a Commands the UPS to perform self testing Press and hold until the buzzer beeps b Battery Load Test Mode Do not hold for 1 second Manual By...

Page 5: ...indicates LED Panel in Error Code Function Mode Overload LED 1 2 1 Indicates UPS is overloaded 2 In Error Code Mode indicates Error Code 16 Site wiring fault LED 1 2 1 Indicates live and neutral lines...

Page 6: ...5 External battery connector 6 AC outlets 7 Utility input circuit breaker 8 AC power connection socket 9 Output circuit breaker for two outlets 4 Rear panel 1 2 3 6 1 2 3 6 5 1 7 8 4 1 2 3 6 8 7 5 9 4...

Page 7: ...UPS while it is still in the plastic bag and check for the following standard package contents 5 Installation 1000 2000VA Schucko French IEC 320 C14 3000VA Schucko French IEC 320 C20 9 8 7 6 9 8 7 6...

Page 8: ...ound To enable the EPO function short pins 1 and 2 Proceed to the installation as follows Please read the condition of use contained in this manual before installing the UPS Start Normal AC mode 1 Bef...

Page 9: ...ress When the self test is completed the UPS will return to AC mode If there were no faults or abnormal conditions then the 1 2 and 1 2 LEDs will turn off Note the main function of self testing is to...

Page 10: ...Bank of stationary maintenance free batteries 5 DC to DC push pull converter control circuit 6 Static bypass loop 7 Input and output EMI filters UPS Status Beep Code UPS faulty Inverter shut down All...

Page 11: ...EDs Normal Working power starts after approximately 5 seconds LEDs on the panel will blink and fans will start Press the ON button 1 2 for 1 5 seconds The UPS starts up normally 1 2 LED ON 1 2 LED ON...

Page 12: ...l turn on the AC DC converter turn off the DC DC converter and switch the charger to charging mode This is the same operating mode as in Figure 5 2 3 During a utility outage the UPS will work as illus...

Page 13: ...e until the load is less than 105 Then the UPS will switch back to Inverter mode automatically 2 The UPS Bypass loop is also equipped with overload protection Its overload capacity is illustrated by t...

Page 14: ...ult 1 2 will shine The UPS will cut off supply to the loads Inverter Current or Voltage Out of Tolerance If the UPS inverter delivers over current or out of tolerance voltage to its outlets then the U...

Page 15: ...UPS software This software can be used for the following functions Automatic shutdown of the local computer UPS parameters reading Connection It is possible to to use RS 232 communication Connect a m...

Page 16: ...obstructing the ventilation louvers Verify that the cooling fans are working properly Contact your local dealer to replace the fans if necessary 4 Site wiring Ground fault 1 2 4 Check if the L and N...

Page 17: ...l receptacle or if the cord plug is faulty 1 Do not use the power strip 2 Replace the wall receptacle cord plug Strange noise or smell Immediately shut down the whole system Disconnect the power from...

Page 18: ...oad LED 1 2 Each LED represents a number as shown in the figure below For example if the 25 50 and 100 bar LEDs are lit the error code is therefore 8 2 1 11 or Er11 which indicates that the UPS is ove...

Page 19: ...gle phase with ground Power Factor 0 98 with full linear load Generator Input Supported Input Connection 10 A IEC 320 C14 16A IEC 320 C20 Output Voltage 230 V Voltage Regulation within 1 until low bat...

Page 20: ...r 10 seconds 150 Immediately shuts down Buzzer continuously alarms Bypass mode 105 continuous 106 120 for 250 seconds shuts down 121 130 for 125 seconds shuts down 131 135 for 50 seconds shuts down 13...

Page 21: ...tton ON Alarm Silence OFF Test Level Button Audible Alarm Battery Mode Sounds once every 1 5 seconds Low Battery Sounds once every 0 2 seconds Overload Sounds once every 3 seconds Normal alarm Sounds...

Page 22: ...x444 322 189 444 Weight 10kg 16 5kg 22 5kg Environmental OperatingTemperature 0 40 C Noise Level 50 dBA Relative Humidity 0 90 without condensation Interface Interface Type RS 232 EPO Slots Dry conta...