Installation and start-up of UPS Keor Hp 200-300kVA
Installation et démarrage de l'UPS Keor Hp 200-300 kVA
Installazione e avviamento UPS Keor Hp 200-300kVA
24
OMD36055 REV. D
Classification of chemically active substances (EN 60721-3-3)
Environmental parameter
Class
3C1R
3C1L
3C1
3C2
3C3
3C4
a)
Sea salt
No
No
No
Salt
fog
Salt
fog
Salt
fog
b)
Sulphur dioxide
[mg/m
3
]
0,01 0,1 0,1 1,0 10 40
c)
Hydrogen sulphide
[mg/m
3
]
0,0015 0,01 0,01 0,5
10
70
d)
Chlorine [mg/m
3
]
0,001 0,01 0,1 0,3 1,0 3,0
e)
H
ydrochloric acid
[mg/m
3
]
0,001 0,01 0,1 0,5 5,0 5,0
f)
H
ydrofluoric acid
[mg/m
3
]
0,001 0,003 0,003 0,03 2,0 2,0
g)
Ammonia [mg/m
3
]
0,03 0,3 0,3 3,0 35 175
h)
Ozone [mg/m
3
]
0,004 0,01 0,01 0,1 0,3 2,0
i)
Nitric oxide (expressed in equivalent values of
nitrogen dioxide) [mg/m
3
]
0,01 0,1 0,1 1,0 9,0 20
Places where atmosphere is strictly monitored and
regulated (“clean spaces” category)
X
Places where atmosphere is permanently
monitored
X
Places located in rural and urban
regions where
industrial activities are few and where traffic
is moderate
X
Places located in urban regions with industrial
activities and/or considerable traffic
X
Places in proximity to industrial sources with
chemical emissions
X
Places located in industrial installations.
Emissions of highly concentrated chemical
pollutants
X
UPS KEOR HP is designed to be installed in an environment that meets the following
classifications.
K Climatic
conditions
In accordance with the technical
specification
B Biological
conditions
3B1 (EN 60721-3-3)
C
Chemically active substances
3C2 (EN 60721-3-3)
S
Mechanically active substances
3S2 (EN 60721-3-3)
In the event that the environmental conditions of the installation room do not comply with the
specified requirements, additional precautions must be taken to reduce excessive values to the
specified limits.