INSTALLATION INSTRUCTIONS

MRIMAS_F-3166_012918

Luminaire 1

Luminaire 2

Luminaire N

(last)

EMI

Filter

EMI

Filter

RED

RED

BLACK

BLACK

VIOLET

GRAY

BLACK

RED

Repeat

Wiring As

Needed

INSIDE MRI ROOM

OUTSIDE MRI ROOM

+

NOTE: ALL WIRES INSIDE MRI ROOM TO BE

INSIDE GROUNDED RIDGID ALUMINUM CONDUIT

0-10V Dimmer

(by others)

COMMON

HOT

MRIPSF-480

MRIFD-1A

(or equal)

120-277VAC

50/60 Hz

AC

IN

+

24V

Figure 7

12. Run DC supply wiring, equal in size and temperature rating to the filter input wiring, between the filter output 

cables and the first luminaire within the shielded room.  Follow recommended wiring layout described within 
Figure 7.  All wiring must be within completely-enclosed, grounded conduit suitable for an MRI environment.  
Any gaps, regardless of size, must be closed or wrapped in copper foil tape.  Special attention should be paid to 
the wiring entry point into the shielded space.  Class 1 wiring methods are required.

13. Run the dimming signal wiring, equal in specification to the filter input wiring, between the filter output cables 

and the first luminaire within the shielded room.  Maintain polarity between input and output sides of the 
filter and follow wiring recommendation in Figure 7.  All wiring must be within completely enclosed, grounded 
conduit suitable for an MRI environment.  Any gaps, regardless of size, must be closed or wrapped in copper foil 
tape.  Special attention should be paid to the wiring entry point into the shielded space.  Cap gray and violet 
leads at luminaire(s) if dimming function is not implemented.

14. Make DC supply and (optional) dimmer control connections within each luminaire. 
15. Reinstall all provided bracketry and internal enclosures provided with the luminaire. These parts are critical to 

the overall EMI shielding of the system.

16. Connect power to external power supply and test for proper operation of lighting system. Make sure all LEDs 

are lit and dimming operation works as intended (if connected).

17. Test operation of lighting during MRI machine idle mode and during scanning operations.
18. Fill out the Installation Registration Form (attached to MRIPSF-480 instruction sheet) and fax to  

Kenall at (262) 891-9701.

Summary of Contents for Kenall MRIMAS Series

Page 1: ... sheet applies for the MRI MedMaster Auracyl Sconce MRIMAS Series A separate instruction sheet is provided in the MRIPSF 480 external power supply system Both sheets are intended to provide comprehensive instructions on fixture installation and wiring The MRI MedMaster Sconce lighting system contains sensitive electronics Take care to avoid damage by improper handling or static electricity dischar...

Page 2: ... closed or wrapped in copper foil tape 10 If a 0 10V dimming circuit is to be connected install at this time The 0 10V dimmer must be installed outside the shielded MRI environment with the Kenall MRIFD 1A dimming line filter or equivalent installed in accordance with the supplied installation instructions Kenall recommends the Lutron Diva DVSTV and Lutron Nova T NTSTV DV series to ensure the full...

Page 3: ... or wrapped in copper foil tape Special attention should be paid to the wiring entry point into the shielded space Class 1 wiring methods are required 13 Run the dimming signal wiring equal in specification to the filter input wiring between the filter output cables and the first luminaire within the shielded room Maintain polarity between input and output sides of the filter and follow wiring rec...

Page 4: ...w kenall com Resources Certified Performance Warranties WARRANTY Figure 8 Standard Luminaire Screw Detail Conclusion of Luminaire Mounting Procedure 19 Reattach the LED tray F to the baseplate C 20 Reattach the reflector wireway with the screws that were removed in step 3 21 Hook the front housing B onto the angle bracket hook D shown in Figure 8 22 Replace the screw s removed in step 1 NOTE Do no...

Reviews: