background image

 

 

 

 

 19

 

 

6.TROUBLESHOOTING 

If the UPS system does not operate correctly, please solve the problem by using the table below.  

Symptom 

Possible cause 

Remedy 

No indication and alarm even though the 

mains is normal. 

The AC input power is not 

connected well. 

Check if input power cord firmly 

connected to the mains. 

The AC input is connected to the 

UPS output. 

Plug AC input power cord to AC 

input correctly. 

The icon 

and 

 

flashing on LCD 

display and alarm is sounding every second. 

The external or internal battery is 

incorrectly connected. 

Check if all batteries are connected 

well. 

Fault code is shown as 27

 

or 28

 and the 

icon 

 

is lighting on LCD display 

and alarm is continuously sounding. 

Battery voltage is too high/low or 

the charger is fault. 

Contact your dealer. 

The icon 

 and

is flashing on 

LCD display and alarm is sounding twice 

every second. 

UPS is overload 

Remove 

excess loads from UPS 

output. 

UPS is overloaded. Devices 

connected to the UPS are fed 

directly by the electrical network 

via the Bypass. 

Remove excess loads from UPS 

output. 

After repetitive overloads, the UPS 

is locked in the Bypass mode. 

Connected devices are fed directly 

by the mains. 

Remove excess loads from UPS 

output first. Then shut down the 

UPS and restart it. 

Fault code is shown as 43 and The icon 

 

is lighting on LCD display and 

alarm is continuously sounding. 

The UPS shut down automatically 

because of overload at the UPS 

output. 

Remove excess loads from UPS 

output and restart it. 

Fault code is shown as 14 and the icon 

 

is lighting on LCD display and 

alarm is continuously sounding. 

The UPS shut down automatically 

because short circuit occurs on the 

UPS output. 

Check output wiring and if 

connected devices are in short 

circuit status. 

Fault code is shown as 0

1, 

02, 03, 04, 11, 

12, 13, 41 and 45 on LCD display and alarm 

is continuously sounding. 

A UPS internal fault has occurred. 

There are two possible results: 

1. The load is still supplied, but 

directly from AC power via bypass. 

2. The load is no longer supplied 

by power. 

Contact your dealer 

Battery backup time is shorter than 

nominal value 

Batteries are not fully charged 

Charge the batteries for at least 5 

hours and then check capacity. If 

the problem still persists, consult 

your dealer.  

 

Batteries defect 

Contact your dealer to replace the 

battery. 

Warning code ” 

 

“ is displayed in LCD 

panel when turn on. 

The internal temperature is too 

high. 

1.

 

Temperature sensor problem. 

Please contact your dealer.  

2.

 

Wait until internal 

temperature cool down. Then, 

turn on the UPS again.  

Summary of Contents for Inform SINUS EVO

Page 1: ...SINUS EVO 1 3 kVA USER MANUAL ...

Page 2: ...mmendation detailed in this manual is necessary to use UPS safely and correctly Units that are labelled with a CE mark comply with the Standard EN 62040 1 and EN 62040 2 Read the manual completely before working on this equipment Keep this manual in UPS s front cover s pocket for easy consultation Reproduction adaptation or translation of this manual is prohibited without prior written permission ...

Page 3: ...amage of the equipment if not followed All packing material must be recycled in compliance with the laws in force in the country where the system is installed PB PROTECTIVE BONDING UPS Uninterruptible Power Systems EPO Emergency Power Off RS232 Serial Communication Protocol SNMP Simple Network Management Protocol CVCF Constant Voltage Constant Frequency V Voltage A Ampere P Power For Input Output ...

Page 4: ... Rear Panel 9 4 2 UPS Input Connection 10 4 3 UPS Output Connection 10 4 4 Communication Connection 10 4 5 Communication Connection 10 4 6 Install Software 10 5 DISPLAY 11 5 1 Button Operation 11 5 2 LCD Panel 11 5 3 Audible Alarm 13 5 4 LCD Display Wordings Index 13 5 5 UPS Setting 13 5 6 Operating Mode Description 17 5 7 Fault Code Table 18 5 8 Warning Indicator 18 6 TROUBLESHOOTING 19 Appendix ...

Page 5: ... and transportation damage and failures after delivery Damage or injuries caused by negligence lack of inspection or maintenance or improper use of the products Faulty electrical wiring Defects arising either from designs or parts imposed or supplied by the purchaser Defects and damage by fire and lightning Failures due to modification in the products without İNFORM approval Improper installation ...

Page 6: ...g wiring outlet In order to fully disconnect the UPS system first press the OFF Enter button to disconnect the mains Prevent no fluids or other foreign objects from inside of the UPS system Do not allow any liquids or any foreign object to enter the UPS Do not place beverages or any other liquid containing vessels on or near the unit This unit intended for installation in a controlled environment ...

Page 7: ... centres A battery can present risk of electric shock and high short circuit currents The following precautions should be observed when working on batteries Remove rings watches necklaces bracelets and all metal objects Only use tools with insulated handles Wear rubbers gloves and a rubber apron when handling batteries Do not lay tools or metal parts on top of batteries Eye protection should be wo...

Page 8: ...ty must be between 20 95 non condensing Recommended storage temperature humidity and altitude values are listed on the Appendix 1 Technical Specifications section If the batteries will be stored for longer than 6 months they shall be charged periodically Charge period depends on the storage temperature as shown below Every 9 months if the temperature is below 20 C Every 6 months if the temperature...

Page 9: ...the delivery document The UPS SINUS EVO packaging protects the equipment against mechanical and environmental damages For greater protection it is also wrapped in a transparent film Check if the following are provided with the equipment UPS User Manual 4 1 Rear Panel Before the installation please check if your UPS is customized following your special requirements if any 1 AC input 2 Input circuit...

Page 10: ...ely affixed Put the small cover back to the rear panel 4 4 Communication Connection Communication port USB port RS 232 port Intelligent slot To allow for unattended UPS shutdown start up and status monitoring connect the communication cable one end to the USB RS 232 port and the other to the communication port of your PC With the monitoring software installed you can schedule UPS shutdown start up...

Page 11: ...in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm selection in UPS setting mode Select Button Switch LCD message Press this button to change the LCD message for input voltage input frequency battery voltage output voltage and output frequency It will return back to default display wh...

Page 12: ...z frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuit Mode operation information Indicates the UPS connects to the mains Indicates the battery is working Indicates the bypass circuit is working Indicates the ECO mode is enabled Indicates the Inverter circuit is working Indicates the output is wo...

Page 13: ...breviation Display content Meaning ENA Enable DIS Disable ESC Escape HLS High loss LLS Low loss BAT Battery CF Converter TP Temperature CH Charger FU Bypass frequency unstable EE EEPROM error 5 5 UPS Setting There are three parameters to set up the UPS Parameter 1 It s for program alternatives Refer to below table Parameter 2 and parameter 3 are the setting options or values for each program Param...

Page 14: ...equency Converter Enable Disable Interface Setting Parameter 2 3 Enable or disable converter mode You may choose the following two options CF ENA converter mode enable CF DIS converter mode disable Default 03 Output Frequency Setting Interface Setting Parameter 2 3 Output frequency setting You may set the initial frequency on battery mode BAT 50 presents output frequency is 50Hz BAT 60 presents ou...

Page 15: ...ault 6V 06 Bypass Enable Disable When UPS İs Off Interface Setting Parameter 3 Enable or disable Bypass function You may choose the following two options ENA Bypass enable DIS Bypass disable Default 07 Bypass Voltage Range Setting Interface Setting Parameter 2 3 Set the acceptable high voltage point and acceptable low voltage point for Bypass mode by pressing the Down key or Up key HLS Bypass high...

Page 16: ... will be only 10 seconds 999 When setting as 999 the backup time setting will be disabled Default 9 Total Battery Ah Interface Setting Parameter 3 Set up total battery AH value of the UPS unit AH 7 999 setting the total battery capacity from 7 to 999 Please set up this figure if external battery pack is connected If the UPS is standard model the default setting is 9AH If the UPS is long run model ...

Page 17: ...ter mode When input frequency is within 40 Hz to 70 Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery under this mode Battery mode When the input voltage is beyond the acceptable range or power failure and alarm is sounding every 4 second UPS will backup power from battery Bypass mode When input voltage is within acceptable range but UPS is overl...

Page 18: ...tage high 12 x Charger failure 45 x Inverter voltage Low 13 x 5 8 Warning Indicator Warning Icon flashing Alarm Low Battery Sounding every second Overload Sounding twice every second Battery is not connected Sounding every second Over Charge Sounding every second Over temperature Sounding every second Charger failure Sounding every second Battery fault Sounding every second Out of bypass voltage r...

Page 19: ...ns Remove excess loads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 and The icon is lighting on LCD display and alarm is continuously sounding The UPS shut down automatically because of overload at the UPS output Remove excess loads from UPS output and restart it Fault code is shown as 14 and the icon is lighting on LCD display and alarm is continuously sou...

Page 20: ...minute 130 3 second Crest Factor 3 1 THD 3 THD linear load 6 THD non linear load Transfer Period Online Mode Battery Mod 0 Inverter Bypass 4 ms typical Battery Mode Waveform Pure Sinus Outputs 1kVA 3 IEC Type 1 Schuko 2kVA 3 IEC Type 1 Schuko 3kVA 3 IEC Type 2 Schuko ECO MOD EXIST Frequency Converter EXIST EFFICIENCY Online Mode 90 Battery Mode 88 BATTERY Battery Type 12 V 9 AH QTY 1kVA 2 x 7 Ah 2...

Page 21: ...0 3kVA 27 6 LCD Display mm 55x27 5 ENVIRONMENTAL Humidity Temperature 95 RH 0 40 C non condensing Acoustic 1m 50dBA COMMUNICATION Standard Smart RS 232 and USB Software Optional SNMP Dry Contact Modbus Maintenance Bypass EPO The manufacturer reserves the rights to change the technical specifications and design without notice ...