background image

10

Raccordement

Addressing

In "addressable" mode, use the BTI interface module as shown in

 the diagram below

IMPORTANT: beyond the BTI interface module, there should only b

e G5 VISION series emergency lighting units in

"addressable" mode.

To connect the BTI interface module, see its accompanying manua

l. A detailed installation and commissioning procedure is

described in the "Installation" section of the manual "Technica

l guide for a URAVISION installation". This manual also gives a

ll the

information on how to create mixed installations containing sta

ndard units and G5 VISION units in "automatic control" or

"addressable" mode..

Commissioning

"Automatic control" mode

Switch on the installation.
Check that the green LED is lit, and also the maintained tube o

f the combined units.

Leave the unit on charge for 1 hr and then switch off the mains

 supply to the units.

Check that the emergency tube lights up.
Switch the installation back on.

"Addressable" mode

A detailed addressing, installation and commissioning procedure

 is described in the "Installation" section of the manual

"Technical guide for a URAVISION installation".
• Commissioning the units and the interface module

As the supervision software is not running, switch on the insta

llation (BTI and emergency lighting units in "addressable" mode

).

If the green and yellow LEDs are flashing alternately (15 s.), 

the BUS is not connected to the emergency lighting unit or the 

poles

have been reversed, check the BUS wiring.
Check that the green LED is lit, and also the maintained tube o

f the combined units (mains power present).

Check that the "battery charging" and BUS LEDs are lit on the B

TI interface module (mains power and voltage present on the BUS

).

• Commissioning the supervisory PC
Install the supervision software on the PC in accordance with t

he instructions in its accompanying manual.

Start up the supervision software and wait for it to scan all t

he units in the installation.

IMPORTANT: check the emergency lighting unit wiring. Any revers

ed wires between the mains power supply and the BUS

will cause irreversible damage to the emergency lighting units 

and the BTI interface module.

Caution: if the wires between the power supply and the BUS are 

reversed, the unit will be damaged permanently.

L=brown

N=Blue

L’=Grey

A+=Red

B-=Black