58
INDICATION
DIAGNOSTIC
SOLUTION
The UPS switches into
stored energy mode and
then back into normal
mode when a connected
device is turned on or the
UPS switches back and
forth between the two
modes.
-
A power strip could be connected to
the UPS. Do not use it.
See also if there is any damage to the
utility wall receptacle or if the cord plug
is faulty. Replace them if needed.
If the problem persists, contact the
LEGRAND Technical Support Service.
Strange noise or smell
-
Shut down immediately the UPS.
Disconnect the mains and contact the
LEGRAND Technical Support Service.
Error code table
ERROR CODE
MEANING
Er05
Battery weak or faulty
Er06
Output short-circuit
Er07
EPO mode
Er11
UPS over-temperature
Er12
Inverter overload
Er14
Fans out of order
Er28
Bypass overload
Er39
Battery problem during the start-up process of the UPS
5 Troubleshooting
Summary of Contents for DAKER DK Plus 3 101 70
Page 9: ...DAKER DK Plus 1 kVA 2 kVA 3 kVA 9 FR 3 2 Configuration Tower 3 2 1 UPS Phase 1 Phase 2 ...
Page 12: ...12 3 Installation Phase 5 Phase 6 ...
Page 39: ...DAKER DK Plus 1 kVA 2 kVA 3 kVA EN 39 3 2 Tower configuration setup 3 2 1 UPS ...
Page 40: ...40 3 2 2 UPS battery cabinet optional 3 Installation S1 ...
Page 42: ...42 3 Installation ...
Page 72: ...72 3 Installazione Fase 5 Fase 6 ...
Page 102: ...102 3 Installation Schritt 5 Schritt 6 ...
Page 132: ...132 3 Instalación Paso 5 Paso 6 ...
Page 162: ...162 3 Монтаж Шаг 5 Шаг 6 ...
Page 184: ...184 Appendix Battery replacement Phase 1 Phase 3 Phase 5 Phase 2 Phase 4 Phase 6 ...
Page 193: ...193 ...
Page 194: ...194 ...
Page 195: ...195 ...