Site Requirements (Plywood-Backed Steel Stud)
1.
Install to plywood-backed steel stud wall using the same instructions as installing to a wood stud wall. See pages 8-9.
Figure 12
Steel Stud (2 x 4 / 25ga minimum)
FRONT
There must be a minimum of
1-7/8" (48mm) clearance
inside wall
16" or 24" (on center) Studs
If back side of wall is unfinished, drywall must be installed
to a minimum of one stud left and right of the stud(s)
being used to install the mount. Drywall must be
secured to studs with screws a maximum of 12" (305mm) apart down center of stud.
Stud type and structural strength must conform to the North American
Specification for the Design of Cold-Formed Steel Structural Members.
5/8" maximum
drywall thickness
(Both Sides of Stud)
[362 S 125 18, C-Shaped, S-Stud Section]
Plywood
1/2" minimum thickness
plywood (5 layers) covered
with drywall having
maximum thickness of 5/8"