LEGRAND 5739 12 Technical Sheet Download Page 6

6

Once the device has been installed, wait two minutes for the self-calibration procedure to be completed. During this period, controls may be automatically sent to the 
system.

!

Configurator in the SET socket 

Behaviour

0

• LED on even if the key has not been configured 
• No status return
• Fade effect enabled

1

• LED on even if the key has not been configured
• No status return
• Fade effect disabled

2

• LED on only if the key has been configured (not configured -> LED off)
• No status return
• Fade effect enabled

3

• LED on only if the key has been configured (not configured -> LED off)
• No status return
• Fade effect disabled

4

• LED on even if the key has not been configured
• Status return enabled
• Fade effect enabled

5

• LED on even if the key has not been configured
• Status return enabled
• Fade effect disabled

6

• LED on only if the key has been configured (not configured -> LED off)
• Status return enabled
• Fade effect enabled

7

• LED on only if the key has been configured (not configured -> LED off)
• Status return enabled
• Fade effect disabled

Use the SET configurator to select:
- if in the idle conditions the unused/not configured LEDs should stay off or on; 
- if the LED should come on when the corresponding key is pressed (status return); for optimum status return effect it is recommended that the LED brightness level is kept low. 
- if the fade effect on the lighting pushbuttons should be enabled or disabled.

LED display selection mode – SET position

LG00047-c-UK

5739 12

5739 13