28
®
8 Technical specifications
COnsTrUCTiOn sPeCifiCATiOns
3 100 87
3 100 88
3 100 89
3 100 90
3 100 91
3 100 92
3 100 93
3 100 94
3 100 95
Power factor range with applied load
From 0,7 to 1
Number of output phases
Single phase
AC-AC conversion efficiency with linear load
PF = 1 and charged batteries
With 50% load
With 75% load
With 100% load
80%
84%
90%
electrical output specifications with battery operation
Nominal output voltage
230V +/-1%
Output frequency
50Hz/60Hz +/-1%
Nominal output power
800 VA
1000 VA
1500 VA
Active output power with linear or
non-linear load PF = 0,7
560 W
700 W
1050 VA
Total harmonic distortion of output voltage
with non-linear nominal load PF=0,7
< 1%
Overload capacity
200% for 15 seconds
Power factor range tolerated with
nominal load
from 0,7 to 1
DC-AC conversion efficiency with linear load
PF=1 and charged batteries
With 50% load
With 75% load
With 100% load
80%
80%
80%
Battery operation
Approximate autonomy in minutes with
charged batteries
50% of the applied load
80% of the applied load
29 min.
17 min.
23 min.
13 min.
5.5 min.
8 min.
Recharge time up to 90% of total load
5-6 hours according to level of discharge
Technical data and quantity of batteries
N° 4 pcs 12V 5,4Ah, sealed, lead-acid,
maintenance free batteries connected
in series
Reserve signal
From 32.2V to 36V can be programmed by
operator
Summary of Contents for 3 100 87
Page 1: ... Part LE05733AA 07 12 01 GF Whad 0 8 1 1 5 kVA Manuel d installation Installation manual ...
Page 16: ...16 ...
Page 30: ...30 ...
Page 44: ...44 ...
Page 58: ...58 ...
Page 72: ...72 ...
Page 86: ...86 Note ...
Page 87: ......