Switch sensor 3-wire - 2000 W
Technical data sheet: S000074408EN-3
Updated: 29/10/2020
Created: 17/12/2012
Clean the surface with a cloth.
Do not use acetone, tar-removing cleaning agents or trichloroethylene.
Resistance to the following cleaning substances:
Hexane (EN 60669-1), Methylated spirit, Soapy water, Diluted ammonia,
Pure bleach diluted to 10%, Window-cleaning products, Pre-impregnated
wipes.
10. STANDARDS AND APPROVALS
Compliant with installation and manufacturing standards.
See e.catalogue.
9. CLEANING
11. TROUBLESHOOTING
8.1 PIR detection (walk-through)
8.2 PIR detection (presence)
8. PERFORMANCE
Sensitivity
Ø (m)
Low (25%)
7
Medium (50%)
8
High (75%)
10
Very high (100%)
12
Sensitivity
Ø (m)
Low (25%)
1
Medium (50%)
2
High (75%)
4
Very high (100%)
5
1,20 m
8 m
4 m
3
m
6
m
8 m
4 m
Caution: Always test before using other special cleaning products.
PROBLEM
CAUSES
SOLUTIONS
Lighting stays on when there is no-one present
Sources of interference can cause false tripping,
such as: air current, vibrations, radiators
1- Reduce the sensitivity level
2- If the interference continues: using the confi-
guration tool, go into the Detection system
parameters, select Maintain and then choose
PIR
3- If the interference still continues, move the
sensor away from sources of interference
Lighting does not switch off during the day
when there is an adequate level of natural light
Regulation function not active
Light level threshold set too high
Light contribution is too high
Activate the regulation function
Reduce the light level threshold
Check that the sensor is positioned correctly in
relation to the window
Decrease the power of the luminaires
Lighting switches off when there are people
present and the natural light level is not ade-
quate (darkness)
Time delay too short
Detection sensitivity too low
Light level threshold too low
Increase the time delay
10 to 1 minutes is recommended for work areas
Increase the sensitivity
Move the sensor closer to the work area
Increase the threshold