Switch sensor 3-wire - 2000 W

Technical data sheet: S000074408EN-3 

Updated: 29/10/2020 

Created: 17/12/2012

 

7.3 Detection parameters

  Time delay: Length of time the load is on after detection. 
 Sensitivity: Detection range setting.

Modes:

 Auto on/Auto off mode: 

Comes on automatically: 

-  At the detection of a presence if there is an insufficient natural level 

of light.

Turns off automatically: 

- If no presence is detected and at the end of the time delay set. 

- Or if the natural light level is sufficient (regulation activated)

Another detection causes automatic switch-on if there is insufficient 

light.

 Walk-through mode:

-   If no presence is detected in the 20 seconds following an initial detec-

tion, the product will cut off the load after 3 minutes.

-  If another presence is detected in the 3 minutes following initial detec-

tion, the device will cut off the load at the end of the set time delay.

  Manual on/Auto off mode:

Comes on via a manual switch, automatic switch off: 

-  Where no presence is detected and at the end of the time delay set.

After switch-off, any new detection within a 30 second period triggers an 

automatic switch-on. The Restart function must be activated.

After 30 seconds the device is switched on via a manual switch.
Detection system:
Initial detection:
 The load is switched on as soon as the first detection 

occurs if the natural light level is below the light level threshold.
Maintain: The load remains active if another presence is detected.
Restard: In manual mode. After switch-off, any new detection within a 

30 second period triggers an automatic switch-on.

After 30 seconds the device must be switched on manually. 
Alarm: an audible signal is emitted before switch-off. (1 minute before, 

then 30 seconds, then 10 seconds).

7. OPERATION 

(continued)

 

7.4 Light parameters

  Light level threshold: Value at which the load comes on if the 

natural light level is less than the setting.

Advanced mode:

   Calibration:  The ambient light level measured with a luxme-

ter must then be transmitted to the sensor (see data sheet  

Cat. No. 0 882 30).

   Regulation  : Automatic switch-off of the load 10 minutes after the 

light level threshold is exceeded with an additional safety threshold 

(to avoid lights switching off at the wrong moment).

Light contribution:  Quantity of additional lux provided by the load 

being switched on. 

 

When the light contribution parameter is set to "Auto" (value 0) on the 

configuration tool Cat. No. 0 882 30 the sensor automatically calculates 

the light contribution.

 

7.5 Modifying the parameters using the configuration tools

• 0 882 35: Simplified configuration tool

 

• 0 882 30: Advanced configuration tool

When the sensor receives an IR command using the configuration tool, 

it emits a beep acknowledging the modification.

For more information about setting parameters, refer to the data sheet 

for the configuration tool Cat. No. 0 882 30.

Range: 1 m.

 

The potentiometers are active by default. Using a configuration tool 

deactivates all the potentiometers.

Reset the product to reactivate them.
-  Restore to factory settings:

1

st

 press: Short press on LEARN: the LED flashes slowly.

2

nd

 press:   Press and hold down LEARN for 10 seconds until the LED 

flashes quickly.

7. OPERATION 

(continued)

Sensor parameters

Default 

value

Modifiable 

parameters

Configuration 

tools

0 882 30 0 882 35

Light level threshold

300 lux

20, 100, 300, 

500, 1000 lux

5 - 1275 lux

A

dv

anc

ed 

mo

de

Calibration

0 - 99995 lux

Regulation

Actif

Activer/

Désactiver

Light

contribution

Auto

Auto - 1275 lux

Caution: At 1275 lux, the device becomes a motion sensor.

Sensor parameters

Default 

value

Modifiable 

parameters

Configuration 

tools

0 882 30 0 882 35

Time delay

15 mn

3,5,10,15,20 

min

5s - 59 min 59s

Sensivity

PIR  

(very high) 

Low, medium,

high, very high

Modes

Auto on/

Auto off

Active

Activate/

Deactivater

Walk-

through 

mode

Inactivr

Activate/

Deactivate

Manual on/

Auto off

Inactir

Activate/

Deactivate

Detection  system

Initial

PIR

Not modifiable

Maintain

PIR

Not modifiable

Restart

PIR

PIR , 

Deactivater

Alarm

Inactive

Activate/

Deactivate