Miniature PIR presence detector - DALI dimming
Technical data sheet: S000104982EN-3
Updated: 03/02/2021
Created: 25/10/2018
Cat. No(s): 0 489 53
7. SETTINGS
(continued)
Parameter
Default
value
Value after
initialisation
Range/
option
Description
General parameters (continued)
Sensitivity Off
8
9
1 (min)
to 9 (max)
Sensitivity level for detecting movement when the detector is off.
On delay
0 minute
-
0 to 99
minutes
The On delay allows the first channel to switch on after the second channel. A typical
application for this would be when a detector is controlling lighting and air condi-
tioning in an area. When the occupant is detected, the lighting will be turned on
immediately, whereas the air conditioning may be turned on after 15 minutes. If the
area is vacated before the detector times out, then the air conditioning will not have
come on. The delay can be set for channel 1 only using this parameter.
Detection mode
Presence
-
Presence
or absence
Presence mode allows the output to turn on when movement is detected and off
when movement ceases. Absence mode allows the output to turn off when move-
ment ceases, but must be manually enabled first.
Lux On Level
999
145
1-950,
999:
OFF
dimming
regulation
Sets a minimum light level below which the PIR sensor is enabled,
allowing the lights to be turned on by movement.
Note: The "Lux Off level" value must always be greater than the "Lux On level” value.
Lux Off Level
999
225
1-950,
999:
disabled
Sets a maximum light level above which the PIR sensor is disabled, preventing the
lights from being turned on by movement.
Lux On time
0
-
0 to 99
minutes
When the ambient light drops below the Lux On Level, this is the delay before
the lights comes on. If at any time during the timed delay the Lux level position is
reversed, the process is cancelled. A minimum time of 15 seconds is defined for a
value of 0. If you try to turn on the lights using a manual control, the lights will come
on regardless of the ambient light level. However, if there is sufficient ambient light,
they will turn off again after the Lux Off time.
Lux Off time
0
1
0 to 99
minutes
When the ambient light exceeds the Lux Off Level, this is the delay before the lights
go out. If at any time during the timed delay the LUX level position is reversed, the
process is cancelled. A minimum time of approximately 15 seconds is defined for a
value of 0.
Dimming parameters
Lux level for
regulation
999
150
1-950,
999:
disabled
Sets a target light level to be maintained by the lighting system
Max value
99%
-
0 to 99%
Maximum dimming output level.
Min value
0%
82%
0 to 99%
Minimum dimming output level.
On value
99%
-
0 to 99%
Dimming output level when switched on (0-99).
Off value
0%
-
0 to 99%
Dimming output level when switched off (0-99). If a non-zero off value is set, the
output will toggle between this value and completely off depending on the switch
level On and Off values. For example, if it is light outside, the fittings will be off if
there is no occupancy. If it is dark outside, they will adopt the preset off value. This
feature is only enabled if “Min value” is set to 99.
Manual control modes
Manual control
mode
✔
-
Shared
2-position
push-button
A single centre-biased retractive switch will be used to control both channels at the
same time.
-
-
Separate
2-position
push-button
-
-
✔
Synchronised
1-position
push-button
A single push-button controls both channels at the same time.
-
-
Separate
1-position
push-button
-