Miniature PIR presence detector - DALI dimming

Technical data sheet: S000104982EN-3 

Updated: 03/02/2021 

Created: 25/10/2018

Cat. No(s): 0 489 53

CONTENTS

 4. CONNECTION

Wire the products as shown in the diagrams. Auxiliary switches are 

optional.

An  auxiliary switch can be used to turn off the light and adjust the 

dimming level (up/down) - on/off.

 5. INSTALLATION

The product is designed to be surface mounted on the ceiling or flush 

mounted, or directly on a luminaire.

The detector should be sited so that the occupants of the room are 

inside the detection area, at a recommended ceiling height of 2.8 m. 

The lower the sensor is installed, the smaller the detection range will be, 

subject to the parameters shown on the detection diagram.
-  For optimum operation of the lux sensor, the lens must be shielded as 

much as possible from the light source.

-  If flush mounting in a panel > 6 mm thick, remove the bottom of the 

retaining clips with a cutter.

- Avoid direct sunlight entering the sensor.
-  Do not site within 1 m of forced air heating or ventilation.
- Do not fix to a vibrating surface.

 

 

  

 

 

 

 

 

 

  

1(ON/UP)

COM

 

Dimming ballast (30 max.)

 

  

Optional push-button for 

manual dimming and 

switch-off control

 

 

 

 

 

 

Sensor head

 

 

  

Use a mains cable for 

the external wiring

 

 

  The maximum cable length between the sensor head and the power unit is 1 metre

 

 

 

 5. INSTALLATION 

(continued)

Flush mounting
The product can be mounted using the flush mounting ring as shown. 

If flush mounting in a material > 6 mm thick, remove the bottom of the 

retaining clips with a cutter.
A 32 mm diameter hole will be required to insert the flush mounting 

ring.

Power-up test procedure
When power is applied to the unit, the load will turn on immediately.
Set the timeout to 10 seconds, vacate the room or remain very still and 

wait for the load to switch off.
Check that the load switches on when movement is detected.
The unit is now ready for programming.

Surface mounted on luminaire or the ceiling
Use the lugs on the back of the detector to secure it into thin sheet 

metal (1 mm max)

Side mounting on luminaire

ø 19.5 mm

3.5 mm

19 mm

32 mm

≥ 6 mm

 6. OPERATION

Detection mode
- Presence: When movement is detected the load will automatically turn 

on. When an area is no longer occupied, the load will switch off 

automatically after an adjustable time period.
- Absence: The load is manually switched on. When an area is no longer 

occupied, the load will switch off automatically after the adjustable time 

period has elapsed.
- Manual control: Short press to turn on, short press to turn off, press 

and hold for dimming cycle.
In either case, Presence/Absence, sensitivity to movement of the PIR 

sensor can be adjusted using the Sensitivity parameter.
HINT: To assist in setting the sensitivity, turn on the

Walk test LED which will flash red when movement is detected.

Switching according to Lux level
Occupancy detection can be made dependent on the ambient light 

level using the Lux On Level and Lux Off Level parameters

Regulation according to light level
The detector measures the overall light level in the detection area, then 

calculates and dims the luminaire lighting to achieve a preset Lux level 

(maintained lighting or daylight harvesting).

Switch on

Switch off

Occupancy

detected

Brighter

 

Darker

 

Lux Off level

 

Lighting level

Lux On time

 

*

**

*

Lux Off time

 

**

Lux On level

Summary of Contents for 0 489 53

Page 1: ...mming commands from the infrared configurator Light level sensor Measures the overall Lux level in the detection area LED status The LED flashes red to indicate the following RJ11 connector The sensor head has an RJ11 socket for connection to the power supply Power supply This power supply has a 6 A relay It also has connections for an auxiliary switch that can be used to turn on the lighting manu...

Page 2: ...ballast 4 Compact fluorescent lamps with separate ferromagnetic ballast 5 ELV halogen lamps with separate electronic ballast 6 Fluorescent tubes with separate electronic ballast 7 Compact fluorescent lamps with built in electronic ballast 8 Compact fluorescent lamps with separate electronic ballast 9 LED lamps with separate electronic ballast 10 LED lamps with built in electronic ballast 2 TECHNIC...

Page 3: ...be required to insert the flush mounting ring Power up test procedure When power is applied to the unit the load will turn on immediately Set the timeout to 10 seconds vacate the room or remain very still and wait for the load to switch off Check that the load switches on when movement is detected The unit is now ready for programming Surface mounted on luminaire or the ceiling Use the lugs on the...

Page 4: ...meters LED operation test Off On or Off When this option is activated a red LED on the sensor flashes when it detects move ment Use this function to check that the sensitivity levels are suitable Inhibit detection No Yes No Disables presence absence detection so that the detector does not control switch ing only dimming Use this mode for light regulation without automatic control according to occu...

Page 5: ... the ambient light drops below the Lux On Level this is the delay before the lights comes on If at any time during the timed delay the Lux level position is reversed the process is cancelled A minimum time of 15 seconds is defined for a value of 0 If you try to turn on the lights using a manual control the lights will come on regardless of the ambient light level However if there is sufficient amb...

Page 6: ...hting Reduce and adjust the value of the Lux Off level parameter in steps of 10 or 20 Example Lux level for regulation 150 Lux On Level 145 Lux Off Level 215 Lux Off Time 1 Min value 82 6 If the light level is too high Reduce and adjust the value of the Lux level for regulation parameter Adjust the value of the following parameters Lux On level Lux level for regulation 5 Lux Off level Lux level fo...