Miniature PIR presence detector - DALI dimming 

Technical data sheet: S000104982EN-3 

Updated: 03/02/2021 

Created: 25/10/2018

Cat. No(s):  0 489 53

128, av. du Maréchal-de-Lattre-de-Tassigny - 87045 LIMOGES Cedex

Tel: +33(0)5 5 55 06 87 87 Fax: +33(0)5 55 06 88 88

www.legrand.com

 1. USE

This miniature PIR (passive infrared) presence detector provides 

automatic control of lighting loads with optional manual control.

This direct dim variant controls DALI or DSI digital dimming ballasts.

The unit detects movement using a PIR sensor and turns the load on. 

When an area is no longer occupied, the load will switch off after an 

adjustable timeout period.

These units come complete with accessories allowing flush mounting in 

suspended ceilings or surface mounting on ceilings, or side mounting 

on a luminaire.

All functionality is fully programmable using an infrared configurator.

 2. TECHNICAL CHARACTERISTICS

PIR sensor

Detects movement within the unit’s detection range, allowing load 

control in response to changes in occupancy.

IR receiver

Receives control and programming commands from the infrared 

configurator.

Light level sensor

Measures the overall Lux level in the detection area.

LED status

The LED flashes red to indicate the following:

RJ11 connector

The sensor head has an RJ11 socket for connection to the power supply.

Power supply

This power supply has a 6 A relay. It also has connections for an auxiliary 

switch that can be used to turn on the lighting manually.

CONTENTS Page

1.  Use. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

2.  Technical characteristics  . . . . . . . . . . . . . . . . . 1

3.  Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

4.  Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

5.  Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

6.  Operation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

7.  Settings  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

8.  Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . 6

9.  Performance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

10. Care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

11. Standards  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

Walk test LED active

 When movement is detected

Valid setting received

 2. TECHNICAL CHARACTERISTICS 

(continued)

Sensor head

Power supply

Dimensions

See dimensions section

Weight

Sensor head: 0.02 kg

Power supply: 0.08 kg

Supply

230 VAC +/-10%

Frequency

50 Hz

Number of ballasts

Up to 30 dimming ballasts

Power consumption

ON 923 mW, OFF 308 mW

Terminal capacity

1.5 mm²

Max. power factor 

correction capacitance

40 μF

Working temperature

-10°C to +30°C

 

5 to 95% non-condensing

Material

Sensor head, side mounting bracket: 

PA (polyamide) Power supply: PA 

(polyamide)

Flush holder: Flame-retardant ABS

Type

Class 2

Protection class

IP 40

PIR lens 

IR receiver

Light level sensor

Status LED

Summary of Contents for 0 489 53

Page 1: ...mming commands from the infrared configurator Light level sensor Measures the overall Lux level in the detection area LED status The LED flashes red to indicate the following RJ11 connector The sensor head has an RJ11 socket for connection to the power supply Power supply This power supply has a 6 A relay It also has connections for an auxiliary switch that can be used to turn on the lighting manu...

Page 2: ...ballast 4 Compact fluorescent lamps with separate ferromagnetic ballast 5 ELV halogen lamps with separate electronic ballast 6 Fluorescent tubes with separate electronic ballast 7 Compact fluorescent lamps with built in electronic ballast 8 Compact fluorescent lamps with separate electronic ballast 9 LED lamps with separate electronic ballast 10 LED lamps with built in electronic ballast 2 TECHNIC...

Page 3: ...be required to insert the flush mounting ring Power up test procedure When power is applied to the unit the load will turn on immediately Set the timeout to 10 seconds vacate the room or remain very still and wait for the load to switch off Check that the load switches on when movement is detected The unit is now ready for programming Surface mounted on luminaire or the ceiling Use the lugs on the...

Page 4: ...meters LED operation test Off On or Off When this option is activated a red LED on the sensor flashes when it detects move ment Use this function to check that the sensitivity levels are suitable Inhibit detection No Yes No Disables presence absence detection so that the detector does not control switch ing only dimming Use this mode for light regulation without automatic control according to occu...

Page 5: ... the ambient light drops below the Lux On Level this is the delay before the lights comes on If at any time during the timed delay the Lux level position is reversed the process is cancelled A minimum time of 15 seconds is defined for a value of 0 If you try to turn on the lights using a manual control the lights will come on regardless of the ambient light level However if there is sufficient amb...

Page 6: ...hting Reduce and adjust the value of the Lux Off level parameter in steps of 10 or 20 Example Lux level for regulation 150 Lux On Level 145 Lux Off Level 215 Lux Off Time 1 Min value 82 6 If the light level is too high Reduce and adjust the value of the Lux level for regulation parameter Adjust the value of the following parameters Lux On level Lux level for regulation 5 Lux Off level Lux level fo...