16
CLASS II
INSULATED CABINETS
IP 43 is achieved by fitting seal Cat.
No. 0 201 30 around the door.
For class II installations, the cables
supplying the control and signalling
units must be treated as class II,
and attached and protected using a
continuous insulated sheath to prevent
them being pulled out and becoming
accidentally detached.
If the control voltage is higher than
50 V, the door must be connected using
an equipotential link conductor, and
the circuits supplying the control and
signalling units must be protected with
devices providing protection against
indirect contact.
The seal must join up at the bottom of the door
A wide range of finishes and accessories:
For more information,
consult workshop specifications EN
61439-1 & 2 available from
www.legrand.com/ecatalogue
4
ACHIEVING IP 43
5
AUXILIARIES ON DOOR
All-metal flat door
All-metal raised door
Glass raised door
Self-adhesive document holder
Cat. No. 0 365 82
Glass flat door
Osmoz control and
signalling units have
a plastic insulated
body and the contact
blocks provide IP 2X
protection