Operation

When properly installed, under the correct operating parameters and properly adjusted, both models 
will operate automatically.  

The correct operating parameters must be present:

Factory pre-set: 107.6°F

T-45NL

Temperature adjustment range: 86°F to 120°F
Cold water supply temperature range: 41°F to 68°F
Hot water supply temperature range: 132.8°F to 149°F
Accuracy of mixed water temperature: +/- 3.8°F
Minimum temperature differential between hot supply and MIX outlet: 21.6°F
Supply pressure: Static: 145 psi
        

Dynamic: 72.5 psi

      Maximum allowable imbalance: 2:1 ratio
   Minimum flow rate: 0.5 gpm

 

@ 0.8 psi 

(see note A)

 

   Maximum flow rate: 15 gpm @ 125 psi 

(see note A) 

T-46NL

Temperature adjustment range: 86°F to 130°F
Cold water supply temperature range: 41°F to 68°F
Hot water supply temperature range: 132.8°F to 149°F
Accuracy of mixed water temperature: +/- 3.8°F
Minimum temperature differential between hot supply and MIX outlet: 21.6°F
Supply pressure: Static: 145 psi
        

Dynamic: 72.5 psi

      Maximum allowable imbalance: 2:1 ratio
   Minimum flow rate: 0.5 gpm @ 0.8 psi 

(see note A)

 

   Maximum flow rate: 15 gpm @ 125 psi 

(see note A)

Note A:  Should not be used for valve selection or system sizing.  The Cv valve listed on the product 

submittal sheet should  be used for valve selection.

Maintenance

Annually inspect the unit for any leakage. Correct as necessary. Annually check the mixed temperature 
supply. Over time, performance could diminish due to hard water conditions or pipe scale causing 
binding of the internal piston. Shut off the water supply and remove the unit by loosening and detaching 
the union ends. Inspect the internal waterways. If they’re clogged with debris, it is likely that the unit’s 
piston is binding.  Immersion and soaking of the unit in the appropriate de-scaling formula should 
restore function. 

DO NOT DISASSEMBLE

 the unit! If after soaking the unit continues to malfunction, 

REPLACE

 the entire unit.

Questions?

  Please contact Legend Technical at 800-752-2082

www.legendvalve.com

866-752-2055

300 N. Opdyke Rd.

Auburn Hills, MI 48326

Summary of Contents for T-45NL

Page 1: ...le fixtures gang showers or hydronic heating loops Before beginning check your local code requirements Select the correct model for your application as it pertains to at the source individual or multiple fixtures point of use or heating systems applications ModelT 45NL Certified in compliance with ASSE 1017 1069 1070 and ANSI NSF 61 ModelT 46NL Certified in compliance with ASSE 1017 and ANSI NSF 6...

Page 2: ...o allow for the removal and servicing of the mixing valve LEGEND T 45NL LEGEND T S 1001NL BALL VALVE COLD WATER SUPPLY Typical domestic water distribution installation HOT MIX H H C C C COLD WATER HEATER Float type Air Vent Air Scoop air purger Boiler Condensing Purging Fill Valves System Circulator Thermometer Expansion Tank 3 Way Thermostatic Mixing Valve Model T 46NL Pressure Differential Bypas...

Page 3: ...ighten the union nuts firmly 4 Pressurize the system and check for leaks Leakage at a union connection may occur if the union nut is over tightened Adjustment T 45NL All adjustments should be performed by a licensed qualified contractor Adjustments must be made while the valve is pressurized 1 Using the forked tool included pry upward at the base of the setting knob until the brass bonnet is expos...

Page 4: ...mplete revolution See photo F 3 Using a 12 MM socket and ratchet turn the stem CLOCKWISE to INCREASE the cold water flow to the mixed outlet LOWERING the delivered water temperature Turn the stem COUNTER CLOCKWISE to INCREASE the hot water flow to the mixed outlet RAISING the delivered water temperature See photo G 4 Using a thermometer placed in the water flow verify the mixed water temperature A...

Page 5: ...ntial between hot supply and MIX outlet 21 6 F Supply pressure Static 145 psi Dynamic 72 5 psi Maximum allowable imbalance 2 1 ratio Minimum flow rate 0 5 gpm 0 8 psi see note A Maximum flow rate 15 gpm 125 psi see note A Note A Should not be used for valve selection or system sizing The Cv valve listed on the product submittal sheet should be used for valve selection Maintenance Annually inspect ...

Reviews: