WATERSWITCH2 INSTALLATION INSTRUCTIONS
|
VERSION 3
PAGE 04
1.4 Enrolling an Extended Range Water Valve Control and Valve Driver (if being installed)
Once the DIPs are set, press and hold the Setting Button UNTIL the Yellow LED comes on and then IMMEDIATELY release the Setting
Button. The Water Valve Control will beep once to confirm that the settings are stored in memory.
DO NOT HOLD THE BUTTON ANY LONGER AS THIS WILL RESET ANY CHANGES MADE TO THE DEFAULT
SETTINGS.
Reassemble Water Valve Control.
If an Extended Range system is being installed, position the Extended Range Water Valve Control and Valve Driver approx. 3 metres away
from each other in line of sight. Press the TEST button on the Valve Control 4 times, holding the button down each time until all the LEDs
illuminate and the Valve Control beeps. The first three times all 3 LEDs will illuminate, on the fourth time the orange WARNING LED will
flash to indicated the Valve Control is in ENROL mode. Please note that occasionally the system will enter ENROL mode after only 2 or 3
presses of the TEST button. As soon as the WARNING LED starts to flash the system is in ENROL mode and you can proceed to the next
step. NB. The TEST button needs to be held down for approx. 4 seconds to operate. Release the button when the Valve Control beeps.
Press the WATER ON button on the Water Valve Control and the red LEAK/FLOW ALARM LED will illuminate.
Press the Enrol button on the Valve Driver (Figure 3) for approx. 3 - 5 seconds and then release it. The Valve Control will emit a short beep
and the Valve Driver will give a long single beep to indicate successful enrolment.
Time
DIP 1
DIP 2
DIP 3
30 minutes
0
0
0
1 hour
1
0
0
1.5 hours
0
1
0
2 hours
1
1
0
4 hours
0
0
1
6 hours
1
0
1
OFF
0
1
1
5 minute test (for engineer use)
1
1
1
0 = OFF / 1 = ON
SET THE ALLOWED CONTINUOUS FLOW TIME LIMIT
Set DIPs 1, 2 & 3 to set the amount of time water may flow
continuously before the Valve closes
If set time is exceeded the Valve will close and the Water Valve
Control will alarm.
FACTORY DEFAULT IF A WATER FLOW SENSOR IS FITTED
= 30 MINUTES
Time
DIP 4
DIP 5
DIP 6
6 hours
0
0
0
12 hours
1
0
0
18 hours
0
1
0
24 hours
1
1
0
36 hours
0
0
1
48 hours
1
0
1
OFF
0
1
1
5 minute test (for engineer use)
1
1
1
0 = OFF / 1 = ON
SET THE ALLOWED NO FLOW TIME LIMIT
Set DIPs 4, 5 & 6 to set the time delay before the Valve closes
when no water flow is detected
If set time is exceeded the Valve will close but the Water Valve
Control will NOT alarm.
FACTORY DEFAULT = OFF
1.3 Water Valve Control – FLOW OR NO FLOW VALVE AUTO CLOSE (Requires installation of a Flow Sensor).
Set using the DIP switches and Setting Button (Figure 1) and with reference to tables below.