  WATERSWITCH2 INSTALLATION INSTRUCTIONS  

|

  VERSION 3

PAGE 04

1.4  Enrolling an Extended Range Water Valve Control and Valve Driver (if being installed)

Once the DIPs are set, press and hold the Setting Button UNTIL the Yellow LED comes on and then IMMEDIATELY release the Setting 

Button. The Water Valve Control will beep once to confirm that the settings are stored in memory.

DO NOT HOLD THE BUTTON ANY LONGER AS THIS WILL RESET ANY CHANGES MADE TO THE DEFAULT 
SETTINGS.

Reassemble Water Valve Control.

If an Extended Range system is being installed, position the Extended Range Water Valve Control and Valve Driver approx. 3 metres away 

from each other in line of sight.  Press the TEST button on the Valve Control 4 times, holding the button down each time until all the LEDs 

illuminate and the Valve Control beeps.  The first three times all 3 LEDs will illuminate, on the fourth time the orange WARNING LED will 

flash to indicated the Valve Control is in ENROL mode.  Please note that occasionally the system will enter ENROL mode after only 2 or 3 

presses of the TEST button.  As soon as the WARNING LED starts to flash the system is in ENROL mode and you can proceed to the next 

step.  NB.  The TEST button needs to be held down for approx. 4 seconds to operate.  Release the button when the Valve Control beeps.

Press the WATER ON button on the Water Valve Control and the red LEAK/FLOW ALARM LED will illuminate.

Press the Enrol button on the Valve Driver (Figure 3) for approx. 3 - 5 seconds and then release it.  The Valve Control will emit a short beep 

and the Valve Driver will give a long single beep to indicate successful enrolment.  

Time

DIP 1

DIP 2

DIP 3

30 minutes

0

0

0

1 hour

1

0

0

1.5 hours

0

1

0

2 hours

1

1

0

4 hours

0

0

1

6 hours

1

0

1

OFF

0

1

1

5 minute test (for engineer use)

1

1

1

0 = OFF / 1 = ON

SET THE ALLOWED CONTINUOUS FLOW TIME LIMIT

Set DIPs 1, 2 & 3 to set the amount of time water may flow 

continuously before the Valve closes

If set time is exceeded the Valve will close and the Water Valve 

Control will alarm.
FACTORY DEFAULT IF A WATER FLOW SENSOR IS FITTED 

= 30 MINUTES

Time

DIP 4

DIP 5

DIP 6

6 hours

0

0

0

12 hours

1

0

0

18 hours

0

1

0

24 hours

1

1

0

36 hours

0

0

1

48 hours

1

0

1

OFF

0

1

1

5 minute test (for engineer use)

1

1

1

0 = OFF / 1 = ON

SET THE ALLOWED NO FLOW TIME LIMIT

Set DIPs 4, 5 & 6 to set the time delay before the Valve closes 

when no water flow is detected

If set time is exceeded the Valve will close but the Water Valve 

Control will NOT alarm.
FACTORY DEFAULT = OFF

1.3  Water Valve Control – FLOW OR NO FLOW VALVE AUTO CLOSE (Requires installation of a Flow Sensor).

Set using the DIP switches and Setting Button (Figure 1) and with reference to tables below. 

Summary of Contents for WaterSwitch2

Page 1: ...LeakSafe solutions TM WaterSwitch2 Installation Instructions ...

Page 2: ... PAGE 02 WATERSWITCH2 COMPONENTS Valve Wireless On Off Switch with delay function Water Flow Sensor Wireless Leak Detection transmitter Leak Detection tape available in 0 3M or 1M lengths and 1 5M connecting cable WaterSwitch2 Valve Control Extended Range Valve Driver ...

Page 3: ... system install 3 x AA batteries in the battery compartment of the Valve Driver the Driver will beep to indicate correct installation If the Valve Driver is to be mains powered drill a cable entry point and connect the mains power adaptor cable to the 12V terminal block as indicated on the PCB Follow the programming Instructions sections 1 2 1 3 and wireless tests sections 1 6 2 1 6 4 before mount...

Page 4: ...pprox 4 seconds to operate Release the button when the Valve Control beeps Press the WATER ON button on the Water Valve Control and the red LEAK FLOW ALARM LED will illuminate Press the Enrol button on the Valve Driver Figure 3 for approx 3 5 seconds and then release it The Valve Control will emit a short beep and the Valve Driver will give a long single beep to indicate successful enrolment Time ...

Page 5: ...TE THE VALVE NB THE WATER ON WATER OFF AND TEST BUTTONS Figure 2 MUST BE HELD DOWN FOR APPROX 4 SECONDS TO OPERATE THE WATER VALVE CONTROL WILL BEEP WHEN A COMMAND IS ACCEPTED 1 Ensure a Valve is connected to input V on the bottom of the Water Valve Control or the connection lead on the valve driver if installed 2 Press and hold down the WATER ON button until it beeps once The green VALVE OPERATIN...

Page 6: ...d insert 2 x AA batteries as shown on the battery holder and reassemble the transmitter will beep 3 times to confirm correct installation Leave the cover off the transmitter whilst you complete the enrolling procedure 2 Press the TEST button on the Valve Control 4 times holding the button down each time until the LEDs illuminate and the Valve Control beeps The first three times all 3 LEDs will ill...

Page 7: ...rom the Water Valve Control press the WATER OFF button on the Switch The Valve Control will beep twice the VALVE OPERATING green LED will flash and the valve will close 2 Press WATER ON to reopen the valve 1 6 3 Installing batteries and enrolling a Wireless On Off Switch 1 Install the CR2032 battery 2 Ensure that the On Off Switch is at least 1M away from the Water Valve Control 3 Press the TEST b...

Page 8: ... installed The Flow Sensor is usually installed after the Valve but can be installed either before or after the valve depending on the available amount of room on the pipe If room permits the Flow Sensor can be connected directly to the valve as shown Figure 7 If space is limited the sensor can be located on the pipe separately to the valve However it must be positioned before any tee off points a...

Page 9: ...which the wireless signal will work will depend on a number of factors including building construction position of the Water Valve Control and Wireless Transmitter and in some instances the effect of interference from other wireless or electronic devices Test the wireless signal between the Wireless Leak Detector Transmitter and the Water Valve Control by temporarily positioning all the components...

Page 10: ...r naturally or with a hairdryer on a medium setting held 1M away from the tape or on a warm not hot radiator 5 Reposition and reconnect the tape once dry 6 Press WATER ON on the Water Valve Control to open the valve 1 2 3 3 To connect the 1 5M connection cable to two or more lengths of leak detection tape with interconnecting 2 core cable between crimp the female bullet connectors at the end of th...

Page 11: ...and at right angles when closed Push operating button down when finished Manual operating button Valve status window Fig 10 4 INDICATORS AND ALARMS 3 4 Manual override on the Motorised Valve LEAK ALARM VALVE OPERATING WARNING 3 3 Isolating a leak and turning the water on Leaksafe recommend you repair all leaks before the mains water is turned back on Where a detected leak is from an appliance e g ...

Page 12: ...the Water Valve Control disconnect the tape then press the WATER OFF button to mute the alarm 2 Identify where in the property the leak has occurred 3 If you have wireless leak detector transmitters installed the one that has instigated the alarm will be beeping If none of the Transmitters are beeping but you have a leak detection tape or tab directly connected to the Water Valve Control then this...

Reviews: