12
Flow test (FT)
FT alarms
Indicates whether the device is monitoring types
of flow or not. If ”Disabled” is selected, the
below mentioned FT alarm times do not have an
effect.
Enabled/
Disabled
FT time Away
The Away mode allows the magnetic valve to
close. It activates the alarm after the water has
flowed longer than the set time of flow.
1-999 s
(20)
FT time Home
Indicates the time that the flow of water is
allowed in Home mode before the flow alarm
sounds. In the Home mode, the magnetic valve
closes if the flow continues for that much longer
that the selected delay time is exceeded.
1-240 min
(20)
FT alarm delay
Indicates the additional time that the flow of
water is allowed in Home mode before the valve
closes.
0-240 min
(5)
Quick test (QT)
QT alarms
Indicates whether Quick test has been activated
or not. If ”Disabled” is selected, the below
mentioned QT alarm times do not have an effect.
Enabled/
Disabled
QT index limit
Indicates the index limit that causes Quick test
to sound an alarm.
0.10-5.00
(1.00)
QT alarm delay
When the quick test alarm sounds, you can set
an additional time that indicates how long the
drip is allowed to continue before the valve
closes.
0-24 timmar
(1)
Tightness test (TT)
TT alarm
Indicates whether Tightness test has been acti-
vated or not. If ”Disabled” is selected, the below
mentioned TT alarm times do not have an effect.
Enabled/
Disabled
TT number
Indicates the number of periods per day when
the tightness test must be approved. If the
number is high, the system should be more
closely monitored.
1-12
(1)
TT duration
Indicates the required duration of the pulseless
period per day in order to approve a tightness
test. If the number is high, the system should be
more closely monitored.
1-60 min
(15)
TT alarm delay
When the tightness test alarm sounds, you can
set an additional time that indicates how long the
alarm is allowed to sound before the valve closes.
0-7 days
(1)