Terminal
Block
LED Driver
(-)
(+)
(LEAD WIRES
TO LED LOAD)
WHITE (NEUTRAL)
GREEN (GROUND)
BLACK (LINE)
AC INPUT
General Wiring Diagram
Installation and Operation
Product Size
Pendant Type
CAUTION: Turn off electrical power at
fuse or circuit breaker box before
wiring fixture to the power supply.
Connecting panels to the AC source
supply:
All units must be individually connect-
ed to the AC supply.
Black = Line
White = Neutral
Green = Ground
Electrical Connection:
1. Loosen the three M5 socket head cap screws with spring washers on the driver housing Cover.
2. The entry hole of the driver housing is 3/4” NPT. Attach to suitable conduit.
3. Run the wire from outside through the conduit and the entry hole of driver housing, and then connect it to
the Terminal Block.
4. Re-attach the housing cover and tighten it with the three M5 socket head cap screws and spring washers
at torque value 5 N-m.
1. Attach the driver housing to the threaded 3/4" pipe and tighten with M4 fastening screws.
2. Connect the electrical part.
3. Re-attach the fixture to the driver housing and tighten it with the three M5 socket head cap screws and
spring washers.
Φ262mm /10.3in
155mm / 6.1in
step1
step2
step3
Set screw
M4
Socket head cap screws
M5
U-Bracket
1. Use the four M8 expansion bolts to attach the bracket to the wall.
2. Connect electrical part.
3. Re-attach the fixture to the driver housing and tighten it with the three M5 socket head cap screws and
spring washers. Adjust the angle of the fixture with the M4 screws.
Ceiling Mount
Stanchion 25°/90°
1. Use the four M8 expansion bolts to attach the bracket to the ceiling.
2. Use the six M4 hexagon socket screws to attach the driver housing to the bracket.
3. Fixture should be hung on the driver housing; connect the wires.
4. Re-attach the fixture and tighten it with the three M5 socket head cap screws and spring washers.
1. Screw the bracket to the pole then tighten the M5 fastening screws.
2. Use six M4 hexagon socket screws to attach the driver housing to the bracket.
3. Connect the electrical part.
4. Re-attach the fixture to the driver housing and tighten it with the three M5 socket head cap screws and
spring washers.
step1
step2
Socket head cap screws
M5
Screws
M4
(Washers induded) M8
Expansion bolts
step3
(Washers induded) M8
Expansion bolts
step1
step2
M4 Socket head cap screws
M4
step3
step4
M5
Socket head cap screws
step1
step2
step3
step4
M4
Socket head cap screws
Screws
M5
M5
Socket head cap screws
Page: 2
Page: 3
LDPI, Inc. 1-800-854-0021 Web: www.ldpi-inc.com E-mail: [email protected]
LDPI, Inc. 1-800-854-0021 Web: www.ldpi-inc.com E-mail: [email protected]
INSTALLATION, OPERATION AND
MAINTENANCE INSTRUCTIONS