background image

 

75.5318.00   20080111 

 

Page 7 of 9 

TROUBLE-
SHOOTING  

COMPANY 
CONTACT 

POWER-ON  
POSITIONING, 
ANGLING AND 
ADJSUTING THE 
MODULES 
(Cont’d). 

 
 
 
 
 
 
 
 
 
 
 

 

‰

 

One notch of the distance adjustment corresponds to approximately 4". 

 

‰

 

If Zone B is too high: Turn the distance adjustment clockwise to increase the detection distance and to 
decrease Zone B. 

 

‰

 

If Zone B is too low, turn the distance adjustment counter-clockwise to decrease the detection distance. 

 

‰

 

Per current ANSI A156.10, the detection zone must be within 28” of the floor. Ideally, each detector should 
be adjusted so that detection occurs at 12” to 16” above the floor. Less than 12” of Zone B may result in 
occasional false triggering of the sensor. 

 

‰

 

Once all sensors have been adjusted, activate the door several times and allow it to go through a full cycle 
each time. Insure that no false triggering is occurring, as would be indicated by the door recycling or 
stopping by itself at any point of travel. 

 

‰

 

Ensure compliance of all applicable safety standards (i.e. ANSI A156.10 / 19). 

 

‰

 

Install all remaining covers, end caps, screws, etc. 

 

 

PROBLEM 

POSSIBLE CAUSE 

CORRECTIVE ACTION 

 

 

 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
Do not leave problems unresolved.  If a satisfactory cannot be achieved after troubleshooting a problem, please contact 
LCN at 1-800-526-2400.  If you must wait for the following workday to call, leave the door inoperable until satisfactory 
repairs can be made.  Never sacrifice the safe operation of the automatic door or gate for an incomplete solution. 
 
 
For more information, visit www.lcn.ingersollrand.com. 
 

Door Mounted Safety 
Sensor does not work at 
all.  No LED indications. 

Faulty power supply 
Faulty connections 

Power supply must be 12 to 24 VAC ± 10% or 
12 to 24 VDC + 10%. 
Check for this power at terminals 7 & 8 of the 
affected DMSS module. 

DMSS output appears to be 
working opposite of what is 
expected. 

Relay output may be configured 
improperly. 

Refer to Appendix for relay configurations.  Be 
sure to observe the LED indications on the 
affected modules to help determine status. 

Door stops by itself before 
reaching the full open position. 

Safety side DMSS may be seeing 
an adjacent wall or rail behind the 
door near the open position. 

Observe the LED status on safety side of door.  
Find the Door Mounted Safety Sensor module 
that is falsely being triggered.  Check for: 

‰

 

Proper detection angle 

‰

 Detection 

range 

adjustment 

Door Mounted Safety Sensor may need to be 
inh bited at a specific point of door travel at the 
safety side for proper operation.  Refer to the 
terminal connections on page 4. 

Detection Distance Adjustment 

Activation or safety is being 
held triggered. 

DMSS detection module may be 
seeing the floor or unwanted 
object near door. 

Reduce the detection range on the affected 
module(s).  Detection should occur at 12” to 
16” above the floor. 

Erratic detection behavior is 
occurring throughout the door’s 
opening and closing cycle. 

Possible faulty wiring at door 
transfer location. 

Check each wire for continuity with as multi-
meter, at the transfer location.  Move the 
wires around during testing to help locate 
any breaks.  Replace faulty wiring as 
necessary. 

33 

Summary of Contents for 8310-804

Page 1: ...ld this angle be interrupted detection will occur Detection is NOT based upon the intensity of the beam and in principle will not be affected by the color or background of the object that interrupts t...

Page 2: ...sion as shown in Picture 2 above Do not use a screwdriver to pry the lens as cracking may occur 4 Picture 3 below shows the angle adjustment clip in its proper position within the extrusion PCB s are...

Page 3: ...to the safety side as shown below Again be sure not to drill through any through bolts or braces within the door A cutaway view below Picture 13 shows wire passage through the door Picture 12 and 14 s...

Page 4: ...0 may be completed Wiring will vary according to the application Available positions on the connector are shown below TERMINAL EXPLANATION OF WIRING CONNECTIONS 1 TST TEST DATA Used with SMR systems o...

Page 5: ...he DMSS lens may then be installed to fit tight against the end cap and plastic sheath to hold it in place as shown in picture 24 Leave the end cap off at the opposite end until all mechanical adjustm...

Page 6: ...is jumper set to Normal Mode Power the sensors up with 12 to 24 VAC 10 or 12 to 24 VDC 10 LED status should reflect what was configured for the relay output Use a white gray or black piece of cardboar...

Page 7: ...complete solution For more information visit www lcn ingersollrand com Door Mounted Safety Sensor does not work at all No LED indications Faulty power supply Faulty connections Power supply must be 12...

Page 8: ...75 5318 00 20080111 Page 8 of 9 APPENDIX WIRING DIAGRAMS...

Page 9: ...75 5318 00 20080111 Page 9 of 9 APPENDIX WIRING DIAGRAMS Cont d...

Reviews: