GUARANTEE

We guarantee the Lawler Mixing Valve to be free from def ects in workmanship and material, and for 

a period of one year from date of purchase, will replace any parts found by us to be defective. We will 

not be held responsible, however, for any labor incidental to, or for any damages caused by defective 

material. Each mixing valve is thoroughly inspected and tested under actual conditions at our factory.

STORAGE

TANK

WATER

HEATER

HEAT TRAP

27” DROP

CW

CW

HW

CV

CV

TO LOW

TEMPERATURE

FIXTURES

Water heater must 
be installed per
manufacturers O+M

CV

MODEL 911

STORAGE

TANK

WATER

HEATER

HEAT TRAP

27” DROP

RECIRCULATION

PUMP

CW

CW

HW

CV

CV

CV

TO LOW

TEMPERATURE

FIXTURES

Water heater must 
be installed per
manufacturers O+M

CV

MODEL 911

Typical Installation Figure 1

When installed at or near the water heater and without a 

recirculation system:

Install the valve as shown in Figure 1 with the mixing valve 

positioned below the hot water tank or heater. If this is not 

possible, pipe in a heat trap as shown.

Typical Installation Figure 2

When installed away from the water heater with a 

recirculating pump on the hot water supply line:

Install the mixing valve as shown in Figure 2. The non-

circulated loop should be limited to 10 feet and must be 

flushed periodically.

Notes:

 If the valve is installed 20 feet or more from the water heater, it is 

important to recirculate the hot water supply to the mixing valve.

The mixing valve must be installed with inlet check valves and the shower 
or the Eyewash/Facewash fixture should be installed 4 to 10 feet from the 
mixing valve. Hot and cold water inlet pressures must be equal. 

Provisions shall be made to thermally isolate the valve.

Figure 1

Valve must be installed with check valves

Figure 2

Valve must be installed with check valves

WARNING: This product contains chemicals known 

to the State of California to cause cancer and birth 

defects or other reproductive harm.
(Installer: California law requires that this warning 

be given to the consumer.)
For more information: www.oehha.org/prop65

CAUTION: The cold water line must be installed so 

that it is not affected by excessively hot ambient 

temperatures. Provisions shall be made to thermally 

isolate the valve. Cold water pipe installed in the 

ceilings of boiler rooms or rooms that increase 

ambient temperature require a recirculating pump.