INSTRUCTIONS MANUAL
-28-
OPERATOR CODE:
Switch the machine on. The MAIN MENU will appear after a few seconds:
Select NEXT MENU:
Select DATA AND CONFIGURAT.:
Select CONFIGURATION:
Select INSERT OPERATOR NO.
It is now possible to input an alphanumeric code (up to 10 characters) that indicates the
number of the operator. This number will appear into all the printouts.
ENABLING TRACER FLUID INJECTION
The optional tracing mechanism may be installed on request on the machine . Follow the
procedure outlined below to enable the option.
Select OPTION from the CONFIGURATION MENU and press ENTER. Type in the code for
enabling tracing. Press key 1 to enable or key 0 to disenable. Press START. After enabling the
tracer, repeat calibration of the oil scale.
DATA AND TIME
The machine holds date and time data in memory for about one year, even if switched off.
Select NEXT MENU, DATA AND CONFIGURAT., CONFIGURATION, and then SET DATE &
TIME. The following screen will be displayed:
Press START to reset the date and time.
hh:mm:ss gg/mm/aa
ENTER CONFIRM
START MODIFY
DATA
CONFIGURATION
SERVICES
PREVIOUS MENU
LANGUAGE
MEASURE UNITS
OPTION
SET DATA & TIME
INSERT OPERATOR N.
AUTOMATIC PROCEDURE
ASSISTED PROCEDURE
NEXT MENU
GAS AVAIL XXXX G
CALIBRATION
DATA AND CONFIGURAT.
SERVICE ALARM
BOTTLE FILLING
Summary of Contents for Value-200
Page 1: ...INSTRUCTIONS MANUAL 1 LAUNCH...
Page 2: ...INSTRUCTIONS MANUAL 2...
Page 183: ...Fig 1 Fig 3 LABEL Fig 2...
Page 184: ...Fig 4 5 3 2 4 1 6...
Page 185: ...Fig 5 a b l f...
Page 186: ...Fig 6 c ps e u v...
Page 187: ...Fig 7 i j k h o z...
Page 188: ...Fig 8 d w n bi m r...
Page 189: ...A2 A5 A3 Fig 9 A1 A6 A4...
Page 190: ...4 MAX min 3 2 1 Fig 10...
Page 191: ...1 3 4 5 Fig 11 2...
Page 192: ...bt Fig 12...
Page 193: ......
Page 194: ......