LAUMAS JOLLY4 Installation & User Manual Download Page 9

 

 

- 6 -

 

INSTRUMENT CALIBRATION CHECK: 

 

Make sure that the container is empty and that the instrument displays zero. Place a significant 
quantity of product in the container (at least 50% of the maximum quantity of product that is to be 
weighed but in any case less than 9,999) and make sure that the instrument displays the correct value.  

-

 

If there is a significant difference between the displayed value and effective amount ( greater 

than 1-2% ) check that this is not caused by a mechanical fault and check the electrical connections 
of the cell and the cell loading position. 

-

 

If the difference is not significant  but around 1-2 %, then proceed to CORRECTING 
DISPLAYED WEIGHT FROM KEYBOARD

 
 

 
CORRECTING DISPLAYED WEIGHT FROM KEYBOARD: 

 

 

When the weight is displayed, press 

. The display will show “CAL I”. Hold down the 

 key 

and press ENTER. The display will show the weight value blinking. Use the 

 

and 

  keys to 

correct it and set the value of the real quantity loaded in the container. Press ENTER to confirm. The 
display will show “CAL I “ for an instant, then the correct value will appear. 

 

If the display shows CAL l ", this means that incorrect values have been set for the 
parameters “CELL”
 and “nU-U”. Repeat the calibration (see THEORETICAL 
CALIBRATION) restoring the laboratory setting
. 

 
 
 

Summary of Contents for JOLLY4

Page 1: ...user s manual version 3 3 JOLLY4 4 different operating modes selectable 2014 30 EU EMC 2014 35 EU LVD DATA TO BE FILLED OUT BY THE INSTALLER Page 1 ENGLISH ENGLISH ENGLISH ENGLISH ENGLISH ENGLISH ENG...

Page 2: ...ication label and or serial number of the product misuse transformation alteration repair of products not carried out by Laumas personnel Laumas provides a 1 year warranty from the date of the deliver...

Page 3: ...V INPUTS OUTPUTS 4 INSTRUMENT START UP 5 THEORETICAL INSTRUMENT CALIBRATION 5 TARE ZERO SETTING 5 INSTRUMENT CALIBRATION CHECK AND CORRECTING DISPLAYED WEIGHT 6 WEIGHT INDICATOR WITH FOUR ALARM THRESH...

Page 4: ...of 4 products Then press ENTER to restore the instruments the selected operating mode appears followed by the version s number If you press ENTER while JOL 4 0 is displayed the JOL 4 message will appe...

Page 5: ...0 ohm or max 8 load cells 700 ohm INTERNAL DIVISIONS 20000 DISPLAY RANGE 999 19999 MEASURING RANGE 4 mV 16 5 mV READING RESOLUTION x 1 x 2 x 5 CONVERSION RATE 10 readings sec LOAD CELLS SIGNAL READING...

Page 6: ...having the same colour perform the same operation for the shields By means of a shielded 4 wire cable with a section not lower than 0 5 mmq connect the terminal board to the JOLLY instrument The cabl...

Page 7: ...message appears press ENTER to close open the relay 1 by ensuring the changeover from to _ _ _ when the relative input changes from open to closed Press the 2 message appears press ENTER to close open...

Page 8: ...ells of 100 kg full scale 100 x 3 300 0 kg 10 of 300 0 kg 30 0 kg Confirm with ENTER the following will appear nU U set the load cell sensitivity expressed in mV V normally 2 000 using the and keys Co...

Page 9: ...the cell and the cell loading position If the difference is not significant but around 1 2 then proceed to CORRECTING DISPLAYED WEIGHT FROM KEYBOARD CORRECTING DISPLAYED WEIGHT FROM KEYBOARD When the...

Page 10: ...he weight for SET 1 max 9999 by using the and keys then confirm with ENTER the following will appear SEt 2 program the weight for SET 2 by using the and keys then confirm with ENTER the following will...

Page 11: ...PAUS time has elapsed the instrument closes the cycle end contact led 4 the gross weight will appears When the unloading phase starts when the minimum weight is reached and the safe time emptying time...

Page 12: ...ce the weight oscillations program a value included between 0 1 and max 9 9 seconds Confirm with ENTER to exit By pressing MENU you can exit in any moment 3CAr PROGRAM Loading batching of 3 products C...

Page 13: ...top of the extractor 0 manual fall or 1 automatic fall The instrument will calculate on itself the fall value by using the arrows keys then confirm with ENTER the following will appear VOL 1 program t...

Page 14: ...ontact led 2 when the SET2 value less the vol2 value is reached the SET2 contact will be opened after PAUS time has elapsed the instrument executes the autotare and closes the SET3 contact led 3 when...

Page 15: ...r VOL 2 value of fall 2 Confirm with ENTER the following will appear VOL 3 value of fall 3 Confirm with ENTER the following will appear VOL 4 value of fall 4 Confirm with ENTER the following will appe...

Page 16: ...product manuals are available online You can download the manuals in PDF format from www laumas com by consulting the Products section or the Download Area Registration is required Think about the en...

Reviews: