background image

START UP 

 

1.  Check proper installation and settings of safety valve, 

high limit cutout(s), low water cut-off and all other 
control and safety devices. Adjust water temperature 
set point on controller to desired value (less than 240 
degrees F). If provided, adjust automatic cutout for 
temperature setting approximately 10 degrees F above 
set point of controller. Manual reset cutout should be 
set approximately 10 degrees above automatic reset 
controller, subject to maximum setting above. 

 
2.  Inspect all controls, wiring, and terminals for possible 

damage during shipment or installation. Make sure 
control circuit switch is in “OFF” position. Check all 
internal wire terminations for tightness. Verify controller 
and sequencer settings. Verify dip switch settings for 
15 seconds “ON” time and 2 seconds “OFF” time, 
delay, and number of stages required.  

 

3.  Open all gauge cocks. Purge piping system of all dirt, 

sludge, and foreign material. Open vessel drain.

 

 

 

4.  Close drain valve. Open all valves in supply and return.

 

 

5.  Fill boiler and piping system with city water. Purge all 

air from vessel and piping system through air vents.

 

6.  As boiler fills check all piping and connections for 

leaks. If necessary, correct immediately before 
proceeding.

 

 

7. Energize circulating pump(s). Check pump rotation. 

Change phases if necessary. Clean pump inlet 
strainers. 

 

 

8.  When boiler is full and flow is established, turn on main 

power disconnect switch.

 

 

9.  Turn on control circuit switch. Pilot lights in control 

panel will come on. Press low water reset button to 
establish control after boiler is filled.

 

 

10. As water temperature increases, check pressure and 

temperature gauges for proper indication. Open vent 
cock again to purge air for the boiler.

 

 

11. After 8 – 24 hours of operation check system water Ph 

with test kit or litmus paper. Ph should read 7.5 to 8.5. 
If test is too acidic (less than 7.0) add neutralizer or 
water treatment.

 

 

12. 

Refer to operation manuals on components 
included at the end of this section for sequencing 
timing, temperature settings etc. 

 

 

 
 

MAINTENANCE 

 

Always disconnect main power to boiler before attempting to service equipment. 

 

1. Routine 

Maintenance 

 

A.  Make visual inspection of all controls. 
 
B.  Check for buzzing contactors in control panel; 

clean or replace if necessary. 

 

C. Observe pressure and temperature gauges for 

normal operation. 

 

D.  Inspect for water leaks at piping connections and at 

element bundle end. 

 
2. Monthly 

Maintenance 

 

A.  Inspect all wiring in control panel and check for 

tightness. 

 
B. Check all piping connections and fittings for 

tightness. 
 

C.  Check boiler water Ph with test kit or litmus paper. 

Ph should read 7.5 to 8.5. 

3. Quarterly 

Maintenance 

 

A.  Check low water cut-off for proper operation. 
 
B.  Check all other valves and controls for proper 

operation.  

 

C.  Check heating element terminations for tightness. 

 
4. Yearly 

Maintenance 

 

A. Shut down entire unit and conduct complete 

inspection. 

 
B.  Access to inspect and clean vessel is obtained 

through inspection opening (element flange). 

 

C.  Replace any defective elements (see next section). 

 

D.  Inspect heating elements for scale. If scale has 

formed, clean with descaling compound such as 
OAKITE DRYCID.  

 

 

4

Summary of Contents for HW

Page 1: ... and 160 psi if model LW boiler Vessels above 250 degrees F and or above 160 psi are designed to ASME Section I or Section VII and are stamped S or U model number designation is HW Heating Elements Removable incoloy sheathed electric heating elements are mounted in 150 lb ASME blind flanges with plated steel compression fittings Complete flange assembly is inserted horizontally into vessel and bol...

Page 2: ... is installed on a level noncombustible surface Lifting lugs welded directly to the pressure vessel are provided 5 Required access see certified print for exact dimensions Front 36 minimum Rear 12 minimum Top 36 minimum Element removal 64 minimum Side opposite element flange 12 minimum 6 Install drain and relief valves 7 Make water inlet and outlet piping connections 8 Wire supply conductors to ma...

Page 3: ...vent a power surge after power interruption the controller will reset automatically to the OFF position when power is restored Normal sequencing then stages the heating elements in accordance with thermostat requirements Gauges Pressure and temperature gauges are mounted on control cabinet front panel Gauges indicate working pressure and temperature of the boiler Safety Valve An ASME pressure reli...

Page 4: ...rol panel will come on Press low water reset button to establish control after boiler is filled 10 As water temperature increases check pressure and temperature gauges for proper indication Open vent cock again to purge air for the boiler 11 After 8 24 hours of operation check system water Ph with test kit or litmus paper Ph should read 7 5 to 8 5 If test is too acidic less than 7 0 add neutralize...

Page 5: ...riven out from the water side of the flange with a drift punch or other suitable tool 12 Install the new element blade through the separator plates and element flange The sheath of the element blade should protrude about 3 4 to 1 inch past the face of the flange 13 Slip the bronze ferrule onto the element blade Screw the compression nut into the flange and tighten to approximately 40 50 Ft Lb torq...

Page 6: ...tons on low water and high limits 2 Water temperature too low Operating control set too low or not operating properly oversized circulator pump or faulty elements fuses contactors wiring 3 Water temperature is too high Operating control is set too high or not operating properly undersized circulator pump or not operating properly 4 Water temperature correct but building is cold Circulator pump not...

Reviews: