Lasermet ICS-5 Wiring Manual Download Page 4

ICS Contactors Wiring Manual 

 

01518-53-000 

Page 4 of 8

 

Issue 2          13 January 2020 

 

 

Concept 

 
When it is necessary for a Lasermet ICS-5 or ICS-6 Interlock Control Panel to switch the mains power 
to  a  laser  or  other  controlled  equipment  the  internal  contacts  of  the  ICS  may  not  be  sufficiently 
rated to switch high powers. In these situations, Lasermet offer a power contactor box. 
 
The contactors are wired so that the supply is turned on when the ‘Arm Laser’ button is pressed and 
the system arms and turned off when the system is disarmed e.g. by opening a door or setting the 
ICS keyswitch to ‘Disable’. 
 
In general, Lasermet supply either 18A or 32A four-pole contactors. The ratings for each type are as 
follows: 
 
18A type AC-3 Rating 18A AC-1 Rating 32A 
230V   4kW 
400V   7.5kW 
690V   10kW 
 
32A type AC-3 Rating 32A AC-1 Rating 50A 
230V   7.5kW 
400V   15kW 
690V   18.5kW 
 
The box contains two contactors whose line contacts are pre-wired in series such that the power to 
the load is cut if either or both contactors open. The ICS monitors both contactors and if one of them 
fails  to  open  when  the  system  is  disarmed,  the  ICS  cannot  be  re-armed.  This  provides  protection 
against the ‘dangerous’ failure of a single contactor. 
 
The contactor box needs to be wired to the line and load cables to be switched, and the box may 
conveniently be located near these. 
 
All  wiring  to  the  contactor  main  terminals  must  be made  using  wire  of current  and  voltage  rating 
appropriate to the power to be carried.  
 
Overcurrent protection devices must be provided on the supply side of the main contacts to protect 
the load, contactors and wiring against excessive current under fault conditions. 
 
The contactors are provided with four-line contacts. For a single-phase installation, use two of the 
contacts only to switch live and neutral. For three-phase installation, use three contacts for the three 
phase lines and the fourth for the neutral. 
 

NOTE:

  Ensure  that  earth  continuity  is maintained at  all times  between  line  and  load  cables  using 

separate earth terminals. The earth must not be switched through the contactors. 
  
It is then necessary to run either one 6-core or two 4-core cables between the ICS-5 / ICS-6 and the 
contactor  box.  These  cables  will  carry  low  current  24V  control  signals,  and  cables  with  7/0.2mm 
stranded copper cores are ideal. Lasermet can supply suitable miniature double-insulated cable with 
a 250V insulation rating, which allows the cables to be run in proximity to 110V/240V mains cables if 
needed.  

Summary of Contents for ICS-5

Page 1: ...ICS Contactors Wiring Manual 01518 53 000 Issue 2 13 January 2020 LASERMET WIRING CONTACTORS TO AN ICS 5 OR ICS 6 WIRING MANUAL Issue 2 ...

Page 2: ...ctors Wiring Manual 01518 53 000 Page 2 of 8 Issue 2 13 January 2020 LASERMET ICS Contactors Wiring Manual Contents 1 Safety Warnings 3 2 Concept 4 3 Testing 6 4 Specifications 7 5 Warranty 7 6 Contact Details 8 ...

Page 3: ...to tamper with the parts open them or use them outside of the parameters contained herein The units are only designed to be fixed to surfaces using their inbuilt fixing holes They must not come into contact with each other or any other moving part when in use The parts should never be subject to impact or mechanical strain Safety switches should never be defeated or bypassed It is imperative that ...

Page 4: ... protection against the dangerous failure of a single contactor The contactor box needs to be wired to the line and load cables to be switched and the box may conveniently be located near these All wiring to the contactor main terminals must be made using wire of current and voltage rating appropriate to the power to be carried Overcurrent protection devices must be provided on the supply side of ...

Page 5: ...rlock equipment including control systems interlock switches illuminated warning signs laser shutters door locks external power supplies etc which can be connected to provide a complete laser interlock system Full support design and installation is available from Lasermet please contact us for any queries Contact details are given at the end of this manual ...

Page 6: ...oltage on the output load terminals of the contactors or on any outlet sockets or at the controlled device e g laser supply input terminals Press the Arm Laser button on the ICS and confirm the Laser Armed indication is lit Verify that both contactors are energised and that the correct voltage is present on all controlled socket outlets and or load equipment supply terminals Disarm the ICS by open...

Page 7: ...es and are not guaranteed Lasermet reserve the right to alter any specification without prior notice 5 Warranty Lasermet provide a 12 month warranty for defects in materials and manufacture from the date of installation or delivery Installations completed by Lasermet are covered against defects in workmanship for 12 months Damage or defects caused by other factors are not covered For example indus...

Page 8: ...vide a complete system We also supply equipment and consultancy covering all aspects of laser safety Full support design and installation is available from Lasermet please contact us for any queries For sales and technical support Lasermet Ltd Lasermet House 137 Hankinson Road Bournemouth BH9 1HR United Kingdom Tel 44 0 1202 770740 Fax 44 0 1202 770730 Email sales lasermet com Website www lasermet...

Reviews: