CHAPTER 3
INSTALLATION
3-1
DT-203P, DT-105P and DT-110P display series
3
INSTALLATION.
The installation of the DT-203, DT-105 y DT-110, is not particularly delicate but some
important considerations must be taken into account.
It must not be anchored to places subject to vibrations, nor should it be installed in places
which generally surpass the limits specified in the display characteristics, both in terms of temperature
and humidity.
The degree of protection of displays DT-203, DT-105 and DT-110 is IP41, meaning that they
are protected against penetration by solid foreign objects of a diameter of about 1mm and against the
vertical fall of water droplets. The DT-203f, DT-105f and DT-110f are IP54, which mean that are more
protected. DT-203e, DT-105e and DT-110e are IP65.
Displays DT-203, DT-105 and DT-110, should not be installed in places with illumination level
higher than 1000 lux. Neither should the display be placed in direct sunlight as visibility would be lost.
Displays DT-105h and DT-110h can be read in sunlight.
In the electrical installation, proximity to lines of high intensity circulation and high voltage lines
must be avoided, as well as proximity to High Frequency generators and U/F converters for motors.
3.1
Power supply.
The power supply must be 88 to 264 VAC 47 to 63Hz or 24VDC with option 24V.
The power supply conductor section will be in line with consumption and the ground conductor
will be a minimum section of 1.5mm².
The power supply connector for 220VAC has 4 contacts and is situated in the lower part of the unit.
Connect the power wires following the schema below
The power supply connector for 24VDC has 5 contacts and is situated in the lower part of the unit.
Connect the power wires following the schema below