Operation/installation 

Transport and storage in original packaging only. National safety and installations regulations and the generally accepted rules

 

of engineering 

practice must be observed when mounting and operating this equipment.

The series of operation head is provided by the company to be used with the series module together.

For the sake of ensuring normal operation and safety of explosion-proof switch modules, user must abide by the following

 

provisions.

Explosion-proof switch module is suitable for use in hazardous areas, zones 1 and 2.

The explosion-proof switch module should be used under he following atmospheric condition: The pressure is

80kPa(0.8bar)-110kPa(1.1 bar). The volume ratio of standard oxygen content is 21% air.

The product should be enclosed in explosion-proof enclosure which is fitted to the environment.

This series of products only can be used together with the actuator attachments manufactured by us.

This series of products should be installed in accordance with IEC60947-5-1.

Proposed tightening screw torque : 0.6 -0.8Nm

The module mounting should be firm and reliable.

Virtual connection is not allowed during the wiring.

During wiring, the creepage distance of bare current-carrying part should be ≥ 12.5mm, electric clearance should be ≥ 8mm.

The component wiring of board back cable type shall be connected with explosion-proof equipment in accordance with its

 

applicable environment.

The flameproof joints are not intended to be required.

The supply terminals are designed for the connection of

≤ 2.Smm' max two brass conductors(IEC60947-7-1). If multi-or fine-ware

connecting cables are used. the wire ends will have to be handled in accordance

with the applicable national and international rules.

The conductor itself shall not be damaged.

The wire should be clamped pretreatment by the standard compression ferrule

before connected to the terminals when wiring (SEE FIGURE 1). If need to connect

two wires, cross-sectional area of the wire should be the same, And should be

clamped pretreatment by the standard compression ferrule respectively (SEE

FIGURE 2).

Accessories/spare  parts 

Use mly original spare parts as well as  original  accessories made by  Larson  Electronics.

Larson Electronics provides  the actuator  for  users  to  select, please  refer  to our  latest  catalogue  for  details.

Maintenance/repairs 

Observe  the  relevant  national  regulations  for  your country.

Only parts from our company that can be used to replace or maintain,  and  the  operation  should  be  carried  out  by professional
electrician!

The  following  points  must  be  checked  during  maintenance:

o

Compliance with permitted temperatures;

o

Cracks in the explosion-proof switch module;

o

Check if the product has been fixed reliably.

o

Check if the wiring is loose.

o

Check if the flame-proof joint is damaged.

Disposal/recycling 

The  respective  valid  national regulations  for waste  disposal shall  be  observed  when  disposing  of  apparatus.

We are pleased to answer any  questions you may have 

p

lease contact  Larson Electronics.