WIRING:

HAL-TRN

 luminaire with Slipfitter:

 

All 480 volt models are inter-

nally prewired.

 

Models with multi-tap ballasts require connecting

 

the black slipfitter lead to the ballast.
• Open 

HAL-TRN

 luminaire by loosening 4 captive screws and

allow the cover to swing down. Remove the three cover screws
covering the ballast compartment. Select the multi-tap ballast
primary lead of the proper voltage and splice to the black slipfitter
lead (see multi-tap caution label on ballast).
• Open slipfitter wiring compartment by loosening 2 screws and
removing compartment cover. Connect slipfitter leads to voltage,
neutral, and ground supply cable conductors.

NOTE:
If post of pole is 25 ft. or higher, the power supply conductor lines
must be supported.
• Loop the power supply lines around the support rod as shown in
Figure 7. Pull line to reduce the size of knot and insert in the
wiring compartment as shown.
• The weight of the supply wire will hold the rod in place.
• Complete the wiring.

FIGURE 7

FIGURE 6

Slipfitter Mount

NOTE: Do Not use on ungrounded 480V circuits.