MAINTENANCE 

CAUTION: 

Always turn OFF AC power to the equipment before servicing. Servicing should be performed only 

by a qualified service technician. Only manufacturer SUPPLIED or APPROVED replacement parts must be 
used. 

1.  BATTERY:

 The battery supplied with this unit requires ZERO maintenance. However it should be tested 

periodically (see TESTING section) and replaced when it no longer operates the connected fixtures for the 
complete duration of a 30-second or 90-minute test. It has a life expectancy of 5-7 yrs when used in a 
normal ambient temperature of 72°F. 

2.  OTHER:

 Clean lenses and replace lamps as, and when, required. 

 

NFPA 101 (Life Safety Code) requires that all emergency lighting equipment be functionally tested every 30 
days for a minimum of 30 seconds and tested annually for full 90-minute duration. Written records of the 
testing are to be kept for examination by the authority having jurisdiction. 

 

TROUBLESHOOTING 

1. 

The emergency lights DO NOT operate and: 

a. 

If the charge indicator light is OFF — Check that the circuit breaker for AC supply is ON. 

b. 

If the charge indicator light is ON: 
 

  Check that the battery is properly connected. 

  If remote lamps are connected to the equipment, then turn OFF the AC supply and disconnect the 

remote circuit wires from the equipment. Turn ON the AC supply and depress the test switch. If the 
local lamps (mounted on the equipment itself) come ON, then check the remote circuit for short or 
overload condition and correct as required. Reconnect the circuit wires and restore AC power. 

  If the local lamps don't turn ON after disconnecting the remote circuit wires, then replace battery. 

 

2. 

Emergency lights are dim — implies battery might not be fully charged. Allow battery to recharge for 24 
hours and then re-test. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

THESE INSTRUCTIONS MAY  NOT COVER ALL DETAILS OR VARIATIONS OF THIS PRODUCT FOR YOUR EQUIPMENT OR INSTALLATION REQUIREMENTS. SHOULD FURTHER 
INFORMATION NOT COVERED BY THESE INSTRUCTIONS BE REQUIRED, PLEASE CONTACT LARSON ELECTRONICS BY EMAIL AT [email protected] OR BY PHONE AT 
1-800-369-6671 FOR FURTHER ASSISTANCE. 