III. Trouble-Shooting and Maintenance

 

 

CAUTION: Always turn AC power to the equipment OFF before servicing. Servicing should be

 

performed only by a qualified service technician.

 

 

I.  Trouble-Shooting

 

 

1. Problem: Emergency lights do not operate. 

If  the  charge  indicator  light  is  OFF,  check

 

that the circuit breaker for AC supply is ON.

 

 

 

If  the  charge  indicator  light  is  OFF,  check 
that they battery is properly connected. If the 
problem persists, replace the battery.

 

 

2. Problem: Emergency lights are dim.

 

 

The battery might not be fully charged. Allow 
battery  to  recharge  for  24  hours  and  then 
retest.  If  the  lights  are  still  dim,  replace  the 
battery.

 

 

II. Maintenance

 

 

 

1. Battery: The battery supplied in the fixture 
requires no maintenance. However, it should 
be  tested  periodically  and  replaced  when  it 
no  longer  operates  the  connected  fixtures 
for the duration of a 30-second or 90-minute 
test.

 

 

2. Other: Clean lenses and replace lamps as 
and when required.

 

 

 

Charger/Battery Fault

 

LED

 

 

Self-Testing: The circuit continuously monitors the operating condition of the AC power, battery supply voltage, 
emergency lamp continuity and  charging  circuit. The purpose  of this option  is to provide  visual signaling  in 
response to a fault at the EXIT sign battery and/or battery charger. If a failure is detected, visual status will 
occur immediately via the CHARGER LED and/or the BATTERY FAULT LED. The LEDs will stay illuminated 
until the fault is corrected. The circuit also monitors the transfer circuit as well as performing automatic code 
compliant testing. The circuit will perform a 30 second discharge and self-test every 28-30 days. A 90 minute 
discharge and self-test is performed every 6 months.

 

 

 

 