EPS-2XPB-SG-600V-LKC

Larson Electronics, LLC

 

  Phone: (800) 369-6671 

 Fax: (903) 498-3364 

  www.larsonelectronics.com 

2

 of 

3

 

INSTALLATION 

1.

Mount the back box by means of mounting lugs. Install conduit nipple and sealing fittings, to be installed on each
conduit entrance or exit to the enclosure back box in Class I and Class II areas. Thread conduit into sealing fitting
(Note: For Class I areas, the conduit should engage [5] full threads.)

2.

The conduit threads should be lubricated with a non-electrical insulating lubricant or pipe joint compound that will
not promote corrosion or chemically attack aluminum.

3.

After conduit system has been properly installed, pull the wires and make electrical connections as required. The
electrical circuits and ground continuity should be checked with an instrument approved for the area. Notice:
Connect only copper wire to this device.

4.

All conduits entering or leaving the enclosure must be sealed within 18” of the enclosure with listed sealing
fittings. Caution must be taken during installation to be sure that the ground flange flame joints of the cover and
box are not scratched, nicked, or damaged. Before assembly of the cover to the box, the mating ground surfaces
of both the box and cover should be wiped clean to assure that the ground flame joint will be free of all foreign
particles such as lint, dust or dirt.

5.

After tightly bolting the cover assembly/assemblies to the enclosure, all box to cover flame joints should be
checked with a 0.0015” thick feeler gauge such that the gauge will not enter the flame path more than 1/8” at any
point.

WIRING 
Standard pigtail(flying leads) wiring 

We strongly encourage a licensed electrician install this product

, in all locations especially in outdoor areas 

where weatherproofing may be required. Universal voltage driver permits operation at 

600V.

Warning: 

Check product label for correct input voltage!

 

Attach supply line wires to the appropriate light fixture wires as shown 

in the diagram 

 

Secure each pair of wires according to the diagram. Utilize a junction box or 

similar  device  and  take  precautionary  steps  for  weatherproofing  all 

connections if installed in a location where water may come in contact with the 

unit. Ensure the unit is properly grounded and that wiring is done according to 

all local and national electrical/building codes.

MAINTENANCE 

All moving shafts should be lubricated 
occasionally to prevent binding. Only use a 
lubricant which is suitable for use with 
aluminum or stainless steel. If devices are 
to be installed in corrosive areas which will 
attack aluminum alloys containing less than 
0.4% copper (boxes and covers) and 303 
stainless steel (mostly shafts), the device 
should be suitably protected from the 
corrosive material.  

CAUTION: 

To prevent ignition of 

hazardous atmospheres, disconnect from 
the supply circuits before opening the 
enclosure; keep tightly closed while circuits 
are energized. 