4.  

Make sure conduit or cable are properly sealed. Electrical components must be kept free of moisture, including

     condensation, at all times.

CAUTION:

 To prevent ignition of hazardous atmosphere, disconnect the device from the supply circuit before opening. 

After de-energizing, delay 10 minutes before opening. Keep assembly tightly closed when in operation.

NOTE: ATEX and IECEx units only:

 The temperature class is determined by the maximum ambient and/or process 

temperature. Units are intended to be used in ambient of -20°C ≤Tamb≤73°C. Units may be used in process 

temperatures up to 133°C providing the enclosure and switch body temperature do not exceed 73°C. The standard 

Temperature Class is T6 Process Temp ≤73°C.
5.  For units supplied with both internal ground and external bonding terminals, the ground screw inside the housing must

     be used to ground the control. The external bonding screw is for supplementary bonding when allowed or required by

     local code. When external bonding conductor is required, conductor must be wrapped a minimum of 180°about the

     external bonding screw. See below.

MAINTENANCE

Inspect and clean wetted parts at regular intervals. The cover should be in place at all times to protect the internal 

components from dirt, dust, and weather, and to maintain hazardous location ratings. Disconnect device from the supply 

circuit before opening to prevent ignition of hazardous atmosphere. Repairs to be conducted by Larson Electronics, Inc. 

Units in need of repair should be returned to the factory.

FRONT VIEW DETAIL

SIDE VIEW DETAIL

CLAMP

SCREW

LOCKWASHER

CONDUCTOR

TERMINAL CONNECTIONS

SPDT

DPDT

PARTS LIST

1.

Cover lock.

2.

External ground.

3.

Enclosure housing and cover.

4.

Terminal block.

5.

Internal ground.

*6.  Magnet arm and switch 

assembly.

7.

Switch body.

*8.  Float, arm and block assembly.

*Approved replacement parts

19-7/32

[488.16]

ATEX/IECEx unit

1-5/8

[41.28]

5

[127.00]

6

[152.40]

8-7/32

[208.76]

5

[127.00]

3

[76.20]

3/4 NPT

1-1/2 NPT

2-

.93]

1/2

[63.50] 3-1

[84

1/32

1

2

3

5

6

Larson Electronics, LLC

 

Phone: (877) 348-9680

 Fax: (903) 498-3364 

  www.larsonelectronics.com 

3

 of 

4

 

Reviews: