background image

EPL-EMG-HB-50LED-RT-WLM

Larson Electronics, LLC

 

  Phone: (800) 369-6671 

 Fax: (903) 498-3364 

 www.larsonelectronics.com 

2

 of 

2

 

OPERATION 

The  emergency  LED  light  works,  mounts  and  is  wired  like  our  EPL-HB-50LED-RT-CM  LED  light 

fixtures.  The  main  differences  are  that  we  add  a  remote  mounted  battery  backup  unit  that  adds 

emergency light functionality to the fixture and the EPL-EMG-HB-50LED-RT-WLM is equipped with a 

wall mounting bracket. This emergency LED light will run at the standard UL suggested 90 minutes 

after  power  is  lost.  The  light  recharges  the  battery  once  electrical  power  is  restored.  Standard 

configuration includes a single emergency battery backup that is automatically recharged and kept in 

a ready state.

 

MAINTENANCE 

Caution: 

To avoid personal injury, disconnect power to the light and allow the unit to cool down 

before performing maintenance. 

Warning: 

No user serviceable parts inside of fixture. Risk of electric shock. Removal of the lens 

will void the warranty. 

1.

Perform visual, mechanical and electrical inspections on a regular basis. We recommend routine checks to be
made on a yearly basis. Frequency of use and environment should determine this.  It is recommended to follow
an Electrical Preventive Maintenance Program as described in NFPA 70B: Recommended practice for Electrical
Equipment.

2.

The  lens  should  be  cleaned  periodically  as  needed  to  ensure  continued  photometric  performance.  Clean  the
lens with a damp, non-abrasive, lint-free cloth. If not sufficient, use mild soap or a liquid cleaner.

3.

Inspect the cooking fins on the luminaire to ensure that they are free of any obstructions or contamination
(i.e. excessive dust build-up). Clean with a non-abrasive cloth if needed.

4.

Do not operate if the lens is cracked or damaged. All fasteners should be properly seated.

BACKUP 

BATTERY

 MAINTENANCE 

Although  no  routine  maintenance  is  required  to keep  the  backup 

battery

 functional,  it  should  be  checked 

periodically to ensure that it is working .The following schedule is recommended: 

1.

Test  the  emergency operation  of  the  fixture  at 30-day  intervals  for  a minimum  of  30  seconds

 by severing power 

to the fixture

. The  lamp  should

 

operate at full illumination.

2.

Conduct  a 90-minute  discharge  test  once  a year.  The  lamp  should  operate  at  full  illumination  for  at least  90

 

minutes.

!!!! REFER ANY SERVICING INDICATED BY THESE 
CHECKS TO QUALIFIED PERSONNEL !!!! 

THESE  INSTRUCTIONS  MAY  NOT  COVER  ALL  DETAILS  OR  VARIATIONS  OF  THIS  PRODUCT  FOR  YOUR  EQUIPMENT  OR  INSTALLATION  REQUIREMENTS. 
SHOULD  FURTHER  INFORMATION  NOT  COVERED  BY  THESE  INSTRUCTIONS  BE  REQUIRED,  PLEASE  CONTACT  LARSON  ELECTRONICS  BY  EMAIL  AT 

[email protected]

 OR BY PHONE AT 1-800-369-6671 FOR FURTHER ASSISTANCE. 

PLEASE VISIT LARSONELECTRONICS.COM FOR 

WARRANTY

 AND 

RETURN

 INFORMATION. 

Wiring Diagram:

Reviews: