During normal operation AC power is applied, the charging indicator light is illuminated, indicating that the 

battery is being charged.  When power fails, the emergency LED driver automatically switches to emergency 

power (internal battery), operating the LED load for a minimum of 90 minutes. When AC power is restored, the 

emergency driver returns to the charging mode.

OPERATION

MAINTENANCE

Although no routine maintenance is required to keep the emergency driver functional, it should be checked 

periodically to ensure that it is working. The following schedule is recommended:

1. Visually inspect the charging indicator light monthly. It should be illuminated. If the charging indicator is 

flashing. Contact tech support.

2. Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds. The LED 

load should operate at reduced illumination.

3. Conduct a 90-minute discharge test once a year. The LED load should operate at reduced illumination for 

at least 90 minutes.

!

 REFER ANY SERVICING INDIC

A

TED BY THESE CHECKS TO QUALIFIED PERSONNEL !

USE AND CARE

Unauthorized modification may impair the function and/or safety of this device and could affect the life of the 

equipment. Always check for damaged or worn out parts before using the device. Store it in a secure place out of the 

reach of children when not in use. Inspect for good working condition prior to storage and before re-use.

 

 

REPLACEMENT PARTS

The 

EMGBALL-LED1-LV

 is designed to provide years of reliable performance. Should the need for replacement parts 

arise, please contact Larson Electronics. 

THESE  INSTRUCTIONS  MAY  NOT  COVER  ALL  DETAILS  OR  VARIATIONS  OF  THIS  PRODUCT  FOR  YOUR  EQUIPMENT  OR  INSTALLATION 

REQUIREMENTS.  SHOULD  FURTHER  INFORMATION  NOT  COVERED  BY  THESE  INSTRUCTIONS  BE  REQUIRED,  PLEASE  CONTACT  LARSON 

ELECTRONICS BY EMAIL AT 

[email protected]

 OR BY PHONE AT 

1-877-348-9680

 FOR FURTHER ASSISTANCE. 

PLEASE VISIT LARSONELECTRONICS.COM FOR 

WARRANTY

 AND 

RETURN

 INFORMATION.

Summary of Contents for EMGBALL-LED1-LV

Page 1: ...EMGBALL LED1 LV INSTRUCTION MANUAL ...

Page 2: ...ISK OF FIRE OR ELECTRIC SHOCK FIXTURE INSTALLATION REQUIRES KNOWLEDGE OF FIXTURE S ELECTRICAL SYSTEMS IF NOT QUALIFIED CONTACT A QUALIFIED ELECTRICIAN BE CERTAIN ELECTRICAL POWER IS OFF BEFORE AND DURING INSTALLATION AND MAINTENANCE MAKE SURE THE SUPPLY VOLTAGE IS THE SAME AS THE FIXTURE S RATED VOLTAGE TO PREVENT WIRING DAMAGE OR ABRASION DO NOT EXPOSE WIRING TO EDGES OF SHEET METAL OR SHARP OBJE...

Page 3: ...t will not be subjected to tampering by unauthorized personnel 15 For Canadian application the output terminals should be in compliance with the accessibility requirement of the Canadian Electric Code 16 This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interfere...

Page 4: ...operate at reduced illumination 3 Conduct a 90 minute discharge test once a year The LED load should operate at reduced illumination for at least 90 minutes REFER ANY SERVICING INDICATED BY THESE CHECKS TO QUALIFIED PERSONNEL USE AND CARE Unauthorized modification may impair the function and or safety of this device and could affect the life of the equipment Always check for damaged or worn out pa...

Page 5: ...RIVERS CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS FIG A TWO 2 WIRE INTEGRATED TEST SWITCH 6 7 7 5 9 2 7 52 1 27 5 9 5 7 7 20021 2 8 5 9 5 5 9 5 2 7 5 5 219 57 5 211 725 52 1 9 2 7 PHUJHQF ULYHU 5 1 FIG B EMERGENCY ONLY 9 2 7 52 1 27 7 7 20021 2 8 2 5 5 219 57 5 211 725 52 1 9 2 7 PHUJHQF ULYHU 3 3 5 1 7 5 3 NOTE For short term testing of the emergency function the battery must be charged for at...

Reviews: