3
Figure 3
Connections Required for System
Larkin S/S 18” x 26” x 8” AFC-DCV Control Box with hinged door and color touch screen display:
A
- Low Voltage wiring to hood sensor(s)
B
-
Wiring to lights in hood(s)
C
-
Fire suppression micro switch wiring
D
-
Two separate circuits wired from breaker panel:
(1)120VAC 15AMP for control voltage
(1)120VAC 15AMP for hood light(s)
E
- 3 Phase power as required wired from breaker panel to Control Box for fan(s) (See wiring diagram)
F
- 3 Phase wired from Control Box to fan(s) (See wiring diagram)
G
- ¼” tubing from pressure sensor in control box to outdoor pick-up.
Note:
If unable to install tubing to pressure
sensor/pick-up contact technical support at 800-322-4036.
*Note:
If Tempered MUA is provided, the tempering lock-out connection must be made from the Control
Box to the tempered unit on terminals R and W1. This prevents tempering when below 50% volume to
ensure proper operation of Tempered MUA units.
H
- *Temperature lock-out connection (if tempered make up air is provided) from Control Box to MUA unit.*
Summary of Contents for AFC-DCV
Page 15: ...15 See Pg 6 ...