background image

 

11 

If the fan(s) and light(s) come on and “Auto Run Mode” is displayed, the temperature sensor in the hood has 
detected a temperature rise. If only the Exhaust fan(s) come on immediately and “FIRE” mode is displayed, check 
for proper connection of Fire System Micro-Switch (See Pg. 6) or check that the Fire Suppression system is not in 
the discharged position.  
 
With the fan button off, depress the light button to energize the hood lights. The light button should illuminate to 
show that the lights are on.  If the hood light(s) are not working:                             

 

1) 

Verify that the bulbs are installed. 

2) 

Verify that all connections to hood(s) have been made and breakers are on. 

          If the light(s) are working properly, de-energize the lights by depressing the light button again.  
 
Turn on the fan(s) by depressing the fan button on the display. The fan and light buttons should illuminate (hood 
lights are interlocked with fan switch). This indicates the fan(s) and light(s) should be operating. “Manual Run 
Mode” should be on the display. If fan(s) are not operating, check all connections to and from the Control Box. 
VFD(s) should start and ramp up to a minimum speed of 18 Hz (the provided keypad should be moved from one 
VFD to another to check proper start-up). The touch screen display should show a 30% output for Exhaust Fan(s), 
building pressure should be green and display ± .01” WC. If an exterior door is opened, the building pressure 
display may read ±.00” WC. 

Note: 

The MUA fan(s) speed is independent of the Exhaust fan(s) speed and is 

controlled by the differential building pressure. A positive (+) increase in building pressure will reduce the MUA 
Fan(s) speed to maintain balanced building pressure. A negative (-) increase will increase MUA Fan(s) speed to 
maintain balanced building pressure. Hood sensor temperature on the display should be approximately the same 
as the room temperature. 

 

Check the rotation of the fan(s). 

Note:

 The exhaust fan(s) will exhaust some air while rotating in reverse. Checking 

rotation may be accomplished in two different ways, (1) you may check the direction arrow on the fan(s) or (2) 
depress the “100% Override” button on the display and monitor the motor amperage displayed in parameter 104 on 
each fan(s) controlling VFD using the VFD keypad (see Setting VFD Parameters Instructions Pg. 12). A fan turning 
in reverse rotation will exceed the rated FLA of the motor. If the amperage displayed in parameter P104 on the VFD 
is higher than the listed FLA for the fan, it is spinning in reverse rotation. To reverse rotation, change any 2 leads 
connected to the VFD output U, V, and W or the rotation may be changed in parameter 400.13 in the VFD using the 
keypad (see Setting VFD Parameters Instructions Pg. 12). 
 

CAUTION! More than one disconnect switch may be required to de-energize the equipment before 
servicing. Ensure all power sources have been disconnected before installing or servicing the system. 
VFD(s) can be holding stored energy when main supply has been switched off. DO NOT touch power 
connections immediately. Check power terminals for isolation from supply.

   

 
See Fan IO&M for further instructions on fan start-up procedures.  
 
After correct rotation has been verified for all fans, if needed, depress the 100% override button again to manually 
run Exhaust fan(s) at 100%. Exhaust fan(s) should be displaying 100% and Pressure display should be a steady 
green. The MUA fan(s) speed is independent of the Exhaust fan(s) speed and is controlled by the building 
pressure. If both Exhaust and MUA fan(s) are running at 100%, but the pressure is not displaying green and 
showing a negative (-) pressure, the maximum Exhaust fan speed may need to be adjusted (See Setting VFD 
Parameter Instructions Adjusting Max Speed Pg. 12).  

 

 

 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for AFC-DCV

Page 1: ...all mount control box includes the following Wall mounted 18 x 26 x 8 stainless steel enclosure with hinged door and tamper resistant latch Color touch screen display mounted on enclosure door for system operation Exhaust and Make Up Air MUA fan s are interlocked If hood fire suppression system is activated the lights and MUA fan s shut down The Exhaust fan s will continue to operate at 100 Temper...

Page 2: ...oused in an 18 x 26 x 8 stainless steel enclosure and should be secured to a fixed wall near the exhaust hood s it controls Fig 1 NOTICE The VFD s produce heat and must have proper ventilation THE AFC DCV ENCLOSURE CAN NOT BE RECESS MOUNTED Fig 1 ...

Page 3: ...l to Control Box for fan s See wiring diagram F 3 Phase wired from Control Box to fan s See wiring diagram G tubing from pressure sensor in control box to outdoor pick up Note If unable to install tubing to pressure sensor pick up contact technical support at 800 322 4036 Note If Tempered MUA is provided the tempering lock out connection must be made from the Control Box to the tempered unit on te...

Page 4: ...nting sensor between a light and the end of the hood may be required on shorter hoods CAUTION If sensor is located too close to a light fixture the heat generated could activate the system The sensor s should be centered between lights Wiring Instructions The Larkin AFC DCV components are all prewired The field wiring required to connect the Control Box to the hood s and breaker panel should be ma...

Page 5: ...pered MUA unit a tempering lock out connection must be connected to the Tempered MUA unit from the control box or the unit may not operate properly see Tempered MUA Unit wiring diagram connections from R and W1 Pg 8 Field Wiring Requirements for Control Panel Control Circuit Field wire 120 VAC 1 Phase 15 AMP circuit to the Control Panel terminals Control Hot CH Control Neutral CN and Ground GND fr...

Page 6: ...nnected to the terminal strip and the dip switch for that sensor is in the off position the auto activation and DCV functions of the system will not be active for that sensor Micro Switch The Larkin AFC DCV requires a Fire Suppression System Micro Switch connection The Micro Switch should be field wired from the Fire Suppression System to the Control Box connecting the Common C lead from the Micro...

Page 7: ...Connect tubing to the Outdoor connection the open port on the pressure sensor The Indoor connection should already have tubing connected to the Indoor Pick Up in the top of the Control Box Note This is required for differential building pressure control If unable to install tubing from the Outdoor Pick Up to the Pressure Sensor in the Control Box contact technical support at 800 322 4036 Fan Input...

Page 8: ...he Control Box to the Tempered MUA unit If this connection is not made the unit may not operate properly Tempered MUA units may not operate properly below a 50 volume This connection allows the Control Box to lock out the heat cool function of the unit when the turn down is below 50 When a Larkin Industries Tempered MUA unit is provided use low voltage wiring from terminal R and W1 in the Control ...

Page 9: ...closed connections C2 NC2 NO2 and C3 NC3 NO3 Contacts are provided for activation of building alarm horn strobe etc Up to 120V 15A power may be connected to C2 and or C3 for activation or de activation of auxiliary controls in Fire Mode The NC2 and NO2 terminals will have whatever voltage has been connected to C2 The NC3 and NO3 terminals will have whatever voltage has been connected to C3 In Fire...

Page 10: ...hunt trip control voltage from the Control Box terminal Shunt Trip Hot STH to the trip terminals on the shunt trip breaker a neutral may be supplied from breaker panel This will provide 120V 1 PH power to trip the breaker in Fire Mode See Pg 9 If a Tempered MUA unit is used connections from the control box to the Tempered MUA unit must be made to terminals R and W1 for control of tempering lock ou...

Page 11: ...ssure Hood sensor temperature on the display should be approximately the same as the room temperature Check the rotation of the fan s Note The exhaust fan s will exhaust some air while rotating in reverse Checking rotation may be accomplished in two different ways 1 you may check the direction arrow on the fan s or 2 depress the 100 Override button on the display and monitor the motor amperage dis...

Page 12: ...eturn to return to the previous menu Adjusting Max Speed The max Exhaust speed will need to be adjusted if the MUA cannot maintain correct pressure Connect the keypad to the VFD controlling the fan to be adjusted Using the above instructions navigate to parameter P430 03 This will display 60HZ If the fan speed needs to be adjusted depress the Scroll Down button to lower the max HTZ of the fan Depr...

Page 13: ...or multiple hood systems when any hood sensor s detects a temperature rise the fan s and light s will automatically energize for all hoods connected to that Control Box Note Allow the system to continue operating after the automatic activation to perform fire system test described below 3 For this portion of the test the system should still be operating in automatic mode described above The system...

Page 14: ...st this system except in extreme cases Please consult factory before attempting any adjustments The microprocessor based controller contains 4 basic adjustments Note Advanced settings are password protected in the menu of the touch screen display If your system is not operating properly do not attempt adjusting controller before contacting customer support at 800 322 4036 The AFC DCV system is des...

Page 15: ...15 See Pg 6 ...

Reviews: